| 2018-09-26 15:32:30 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. THE SINKS IN THE BREAKROOM AND THE CARD ROOM SHALL |
| | COMPLY WITH FBC ACC WHERE SINKS ARE PROVIDED, AT LEAST |
| | 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED |
| | IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606. |
| | 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING |
| | WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE |
| | AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED |
| | 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED |
| | WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER |
| | SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR |
| | GROUND. |
| | |
| | 2. SHT. P-1.3.01 THE 3" HUB DRAIN IN THE MECHANICAL |
| | RECEIVING DISCHARGE FROM THE AC UNITS IS A CODE |
| | VIOLATION CONDENSATE SHALL NOT DISCHARGE INTO THE |
| | SANITY SYSTEM. PER WPB CODE OF ORDINANCES SEC. |
| | 90-126(5) |
| | |
| | 3. PROVIDE AN ENGINEERED DETAIL FOR WATER HEATER SHELF |
| | . WPB AMEND TO FBC 107.2.1 |
| | |
| | 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES |
| | AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET |
| | FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND |
| | VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN |
| | APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT |
| | CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5 |
| | |
| | 5. PLEASE PROVIDE A WATER AND SANITARY ISOMETRIC |
| | DRAWINGS. PER WPB AMEND TO FBC 107.3.5.1.3(13) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |