Plan Review Notes
Plan Review Notes For Permit 18080365
Permit Number 18080365
Review Stop P
Sequence Number 1
Notes
Date Text
2018-09-26 15:32:301ST REVIEW:
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 1. THE SINKS IN THE BREAKROOM AND THE CARD ROOM SHALL
 COMPLY WITH FBC ACC WHERE SINKS ARE PROVIDED, AT LEAST
 5 PERCENT, BUT NO FEWER THAN ONE, OF EACH TYPE PROVIDED
 IN EACH ACCESSIBLE ROOM OR SPACE SHALL COMPLY WITH 606.
 606.2 CLEAR FLOOR SPACE.A CLEAR FLOOR SPACE COMPLYING
 WITH 305, POSITIONED FOR A FORWARD APPROACH, AND KNEE
 AND TOE CLEARANCE COMPLYING WITH 306 SHALL BE PROVIDED
 606.3 HEIGHT.LAVATORIES AND SINKS SHALL BE INSTALLED
 WITH THE FRONT OF THE HIGHER OF THE RIM OR COUNTER
 SURFACE 34 INCHES MAXIMUM ABOVE THE FINISH FLOOR OR
 GROUND.
  
 2. SHT. P-1.3.01 THE 3" HUB DRAIN IN THE MECHANICAL
 RECEIVING DISCHARGE FROM THE AC UNITS IS A CODE
 VIOLATION CONDENSATE SHALL NOT DISCHARGE INTO THE
 SANITY SYSTEM. PER WPB CODE OF ORDINANCES SEC.
 90-126(5)
  
 3. PROVIDE AN ENGINEERED DETAIL FOR WATER HEATER SHELF
 . WPB AMEND TO FBC 107.2.1
  
 4. TEMPERED WATER SHALL BE DELIVERED FROM LAVATORIES
 AND GROUP WASH FIXTURES LOCATED IN PUBLIC TOILET
 FACILITIES PROVIDED FOR CUSTOMERS, PATRONS AND
 VISITORS. TEMPERED WATER SHALL BE DELIVERED THROUGH AN
 APPROVED WATER-TEMPERATURE LIMITING DEVICE THAT
 CONFORMS TO ASSE 1070 OR CSA B125.3. PER FBC PL 416.5
  
 5. PLEASE PROVIDE A WATER AND SANITARY ISOMETRIC
 DRAWINGS. PER WPB AMEND TO FBC 107.3.5.1.3(13)
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  