| 2018-09-21 13:32:41 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18080365 |
| | 1ST REVIEW: SEPTEMBER 21, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | |
| | 1.[FBC AMENDED 107.2.5]REMOVE SHEET A-1.1.01 |
| | ARCHITECTURAL SITE PLAN. THE UDK PLAN IS THE APPROVED |
| | SITE PLAN FOR THIS PROJECT AND IT IS ALREADY UPLOADED. |
| | |
| | 2.[FL. STATUTE 472.025]SURVEY TO BE SEALED BY THE |
| | SURVEYOR OF RECORD (SEE SIGNATURE REVIEW) |
| | |
| | 3.[FBC AMENDED 110.3(A)1.1]A FOUNDATION/FORM BOARD |
| | SURVEY PREPARED AND CERTIFIED BY A REGISTERED SURVEYOR |
| | MAY BE REQUIRED, PRIOR TO APPROVAL OF THE SLAB |
| | INSPECTION. THE SURVEY SHALL CERTIFY PLACEMENT OF THE |
| | BUILDING ON THE SITE, ILLUSTRATE ALL SURROUNDING |
| | SETBACK DIMENSIONS AND SHALL BE AVAILABLE AT THE JOB |
| | SITE FOR REVIEW BY THE BUILDING INSPECTOR. |
| | FL. PLAN A-1.3.01 SHOWS 19.00 F.F.E. CIVIL PLANS ARE IN |
| | NGVD29. |
| | IF THE FLOOR PLAN IS IN NAVD88 THAN USE CONVERSION FROM |
| | NGVD29 TO NAVD88. |
| | |
| | 4.[FBC AMENDED 109]COST EVALUATION IS LOW FOR THE |
| | SQUARE FOOT COST OF CONSTRUCTION. PLEASE PROVIDE |
| | DOCUMENTATION OF HOW THIS NUMBER WAS DERIVED. CURRENT |
| | ICC COST EVALUATION FOR VB CONSTRUCTION IS $133.67 PER |
| | SQ. FT. FOR BUSINESS AND $127.52 FOR A-3 ASSEMBLY. |
| | |
| | 5.[FBC ENERGY C401.2]APPLICATION. |
| | COMMERCIAL BUILDINGS SHALL COMPLY WITH ONE OF THE |
| | FOLLOWING: |
| | 1)THE REQUIREMENTS OF ANSI/ASHRAE/IESNA 90.1, EXCLUDING |
| | SECTION 9.4.1.1(G) OF THE STANDARD. |
| | 2)THE REQUIREMENTS OF SECTIONS C402 THROUGH C405. IN |
| | ADDITION, COMMERCIAL BUILDINGS SHALL COMPLY WITH |
| | SECTION C406 AND TENANT SPACES SHALL COMPLY WITH |
| | SECTION C406.1.1. |
| | 3)THE REQUIREMENTS OF SECTIONS C402.5, C403.2, C404, |
| | C405.2, C405.3, C405.5, C405.6 AND C407. THE BUILDING |
| | ENERGY COST SHALL BE EQUAL TO OR LESS THAN 85 PERCENT |
| | OF THE STANDARD REFERENCE DESIGN BUILDING. |
| | |
| | 6.[FBC 107.2.5]ADD SHEET A-0.0.02 TO INDEX. THIS SHEET |
| | WILL RECEIVE DIGITAL STAMP FOR BUILDING REVIEW AND I |
| | WOULD LIKE ALL SHEETS PROVIDED TO BE LISTED ON THAT |
| | PAGE. |
| | |
| | 7.[FBC TABLE 1017.2]UPDATE MAX. TRAVEL DISTANCE CHART |
| | FOR THE OCCUPANCIES FOR B-BUSINESS AND A-3 ASSEMBLY. |
| | ALSO, UPDATE GENERAL NOTES AND LIFE SAFETY NOTES TO |
| | REFLECT LIFE SAFETY SYSTEMS TO BE USED IN THIS |
| | BUILDING. |
| | |
| | 8.[FBC 1609.6.4.4.1]COMPONENTS AND CLADDING. |
| | SHEET S-4.01 UPDATE CODE REFERENCES TO FBC 2017 6TH |
| | EDITION. |
| | PROVIDE +/- PRESSURES FOR EACH OPENING. |
| | |
| | 9.SHEET A-3.2.01 SHOWS 3X10 WOOD RAFTERS AND CALLS OUT |
| | TO SEE STRUCTURAL FOR ATTACHMENT. SHEET S-3.01 SHOWS |
| | CONCRETE PORTION. PLEASE SHOW STRUCTURAL CONNECTIONS OF |
| | THE 3X10?S. |
| | |
| | 10.SHEET A-3.2.02 CALLS OUT 5/8 PLYWOOD, BUT STRUCTURAL |
| | SHEET S-2.02 IS CALLING 3/4. PLEASE CO-ORDINATE THE |
| | PLYWOOD SIZE. |
| | |
| | 11.[FBC TABLE 1604.3]PROVIDE DEFLECTION LIMITS OF |
| | TRUSSES. |
| | |
| | 12.[FBC 1507.4.2]DECK SLOPE. THE MINIMUM SLOPE FOR |
| | LAPPED, NONSOLDERED SEAM METAL ROOF PANELS WITHOUT |
| | APPLIED LAP SEALANT SHALL BE THREE UNITS VERTICAL IN 12 |
| | UNITS HORIZONTAL (25-PERCENT SLOPE). |
| | ADD NOTE THAT METAL PANELS ON 2/12 PITCH WILL HAVE |
| | APPLIED LAP SEALANT. |
| | |
| | PRODUCT APPROVALS: |
| | |
| | 13.[FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR |
| | WINDOWS AND DOORS, OR INDICATE THAT YOU WOULD LIKE THEM |
| | DEFFERED. |
| | |
| | 14.[FBC AMENDED 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR |
| | ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED. |
| | |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |