2018-09-14 08:03:01W.P.B. PERMIT: 18080276 (GARAGE)
 REVIEWED: SEPTEMBER 13, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC A = AMENDMENTS TO THE FLORIDA BUILDING CODE,6TH
 EDITION (2017)
 FBC B = FBC BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 [FBC AMENDED 105]SEPARATE PERMIT THROUGH ENGINEERING
 FOR DRIVEWAY ACCESS. CONTACT 561-494-1040, OR ON THE
 WEB: HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUBLIC-
 WORKS/ENGINEERING-SERVICES
  
 1. [FBC 107.2.5]SHEET 1 WIND INFORMATION-REMOVE LEVEL
 OF ALTERATION 2. THIS WOULD BE NEW CONSTRUCTION R-3.
  
 2. [FBC R301.4]DEAD LOAD AND[FBC R301.5]LIVE LOAD
 PROVIDE LOADS FOR FLOORING AND LOADS FOR ROOFING ON
 SHEET 4.
  
 3. [FBC AMENDED 107.2.1.2]PROVIDE TWO COPIES OF PRODUCT
 APPROVAL FOR GARAGE DOOR.
  
 4. [FBC 107.3.4.1]A CONSTRUCTION GUARDRAIL DETAIL,
 PREPARED BY A DESIGN PROFESSIONAL LICENSED UNDER FS471
 OR FS481, IS REQUIRED TO BE SUBMITTED, REVIEWED AND
 ISSUED BY THE CITY OF WEST PALM BEACH, OR INDICATE THAT
 IT WILL BE DEFERRED.
 *SUBJECT TO THE INSPECTOR'S DISCRETION, THIS MAY BE
 ACCEPTED IN THE FIELD AT TIME OF INSPECTION.
  
 5. [FBC AMENDED 107.3.4.1]SUBMIT TRUSS SHOP DRAWINGS,
 OR INDICATE THAT THE SUBMITTAL WILL BE DEFERRED.
 DEFERRED SUBMITTALS TO BE REVIEWED PRIOR TO
 INSTALLATION.
  
 6. [FBC R3-1.2(6)]PROVIDE ROOFING WIND DIAGRAM THAT
 MATCHES THE ROOF CONDITION OF THIS HOUSE FOR ZONES
 1,2,& 3.
  
 7. [FBC R304.2]MINIMUM DIMENSIONS.
 HABITABLE ROOMS SHALL BE NOT LESS THAN 7 FEET (2134 MM)
 IN ANY HORIZONTAL DIMENSION. ALSO, LABEL EGRESS WINDOW
 FOR THE BEDROOM.
  
 8. [FBC 107.2.5]SHEET 2: 1/2 STAIR DETAIL. WITH THE
 WEIGHT OF WOOD STAIRCASE VERIFY IF THE 4? SLAB IS
 SUFFICIENT BEARING.
  
 9. [FBC 107.2.5]SHEET 4:
 A.UPDATE CONNECTOR H10A TO REFERENCE CURRENT FL 10456.2
 B.FLOOR FRAMING PLAN REFERANCES SECTION 2/5 AT BALCONY,
 BUT THIS DETAIL IS FOR STAIRS WITH POSTS. PROVIDE
 DETAIL FOR CANTILEVER BALCONY INSTEAD OF STAIR LANDING.
  
 10. [FBC 107.2.5]SHEET 5: SECTION 2/5 SECOND FLOOR
 BALCONY. 5/8 CDX PLYWOOD IS CALLED OUT UNDER THE
 DECKING MATERIAL. ID THIS EXTERIOR GRADE AND HOW ARE
 EDGES PROTECTED FROM WATER?
  
 11. [FBC R309.1]FLOOR SURFACE.
 THE AREA OF FLOOR USED FOR PARKING OF AUTOMOBILES OR
 OTHER VEHICLES SHALL BE SLOPED TO FACILITATE THE
 MOVEMENT OF LIQUIDS TO A DRAIN OR TOWARD THE MAIN
 VEHICLE ENTRY DOORWAY.
  
 12. [FBC ENERGY R401.2]PROVIDE ENERGY CALCULATIONS TO
 MEET REQUIREMENTS IN R401.2 RESIDENTIAL ENERGY CODE.
 CHOOSE METHOD IN R401.2 AND SUPPLY DOCUMENTATION.
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
  