| 2018-09-25 10:17:27 | RESIDENTIAL (R3) MECHANICAL SECOND REVISION REVIEW |
| | CHECKLIST. |
| | CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | (1)- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS |
| | SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC. |
| | R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| | |
| | RESPONSE: |
| | EQUIPMENT SIZING CALCULATIONS SUBMITTED ARE FOR THE |
| | WRONG ADDRESS. THIS IS 245 EDMOR RD NOT 241 EDMOR RD. |
| | PROVIDE CALCULATIONS FOR THE CORRECT HOUSE. SEC. |
| | 107.2.1 CITY AMENDMENTS. |
| | |
| | ORIGINAL COMMENT: |
| | (2) GUEST BEDROOM ON THE 1ST FLOOR DOESN'T COMPLY WITH |
| | THE BALANCED RETURN AIR SEC. M1602.4 FBC-RESIDENTIAL. |
| | PROVIDE TRANSFER DUCT OR GRILL AND SPECIFY SIZE. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. PLANS SUBMITTED WERE NOT REVISED. |
| | |
| | ORIGINAL COMMENT: |
| | (3) THERE ARE SOME SUPPLY AIR REGISTERS ON THE FIRST |
| | AND SECOND FLOOR THAT ARE MISSING THE DUCT SIZE AND |
| | SIZE OF REGISTER. PROVIDE COMPLETE INFORMATION., SEC. |
| | 107.3.5.3(10) CITY AMENDMENTS. |
| | |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. PLANS SUBMITTED WERE NOT REVISED. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| | |
| | |