| 2018-09-25 11:27:28 | 1- REMAINDER: BUILDING REVIEW WAS ALSO APPROVED ON |
| | 01/23/18 WITH PROVISO. PROVIDE INFORMATION REQUESTED ON |
| | PROVISO TO AVOID CONFLICTS/DELAYS. SEE COPY OF BUILDING |
| | PROVISO BELOW: |
| | |
| | BUILDING REVIEW APPROVED WITH PROVISO: |
| | (1)- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN |
| | CREDIT. REVISE GREAT ROOM CEILING FAN SIZE TO COMPLY |
| | WITH SEC. R405.7.6 FBC-ENERGY CONSERVATION. |
| | |
| | RESPONSE: |
| | REPEAT COMMENT. NOT ADDRESSED. |
| | |
| | |
| | (2)- PROVIDE PRODUCT APPROVAL FOR THE OVERHEAD GARAGE |
| | DOOR THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE |
| | ARCHITECT ON SHEET A-301. (OK. SEE REVISION 18091139) |
| | |
| | RESPONSE: |
| | DESIGN PRESSURES OF GARAGE DOOR NOA 15-0908.08 DON'T |
| | MEET THE DESIGN PRESSURES CALCULATED BY THE ARCHITECT |
| | ON SHEET A-301. NEED PRODUCT APPROVAL THAT MEETS OR |
| | EXCEEDS CALCULATED DESIGN PRESSURES. |
| | |
| | (3) DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT |
| | APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: PLEASE |
| | PLACE THE REVIEW STAMP ON THE FRONT OF THE PRODUCT |
| | APPROVAL NOT ON THE BACK. |
| | |
| | |
| | ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH |
| | COMMENT TO HELP EXPEDITE THE REVIEW PROCESS. |
| | |
| | ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD |
| | DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY |
| | REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS. |
| | |
| | |