2018-08-13 09:13:43RESIDENTIAL (R3) MECHANICAL REVISION REVIEW COMMENTS
 CODE: FBC 5TH EDITION (2014) AND CITY AMENDMENTS.
  
 1- REVISION FEES ARE NOT PAID. NEED TO PAID THE
 REVISION FEES INCLUDING THE ADDITIONAL FEES FOR REVISED
 DRAWINGS ADDRESSING COMMENTS BELOW. NOTE: REVISION
 RE-SUBMITTAL WILL NOT BE REVIEWED UNTIL ALL FEES ARE
 PAID.
  
 2- ORIGINAL MECHANICAL REVIEW WAS APPROVED ON 01/23/18
 WITH A PROVISO. COMPLETE EQUIPMENT SIZING CALCULATIONS
 WERE REQUESTED AND WERE NOT SUBMITTED. A/C PLAN WAS
 REVISED BUT SIZING CALCULATIONS WERE NOT SUBMITTED.
 PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS. SEE
 COPY OF PROVISO BELOW.
  
 MECHANICAL REVIEW APPROVED WITH PROVISO:
 (1)- PROVIDE COMPLETE EQUIPMENT SIZING CALCULATIONS
 SHOWING COMPLIANCE WITH ALL THE REQUIREMENTS OF SEC.
 R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
  
  
 3- GUEST BEDROOM ON THE 1ST FLOOR DOESN'T COMPLY WITH
 THE BALANCED RETURN AIR SEC. M1602.4 FBC-RESIDENTIAL.
 PROVIDE TRANSFER DUCT OR GRILL AND SPECIFY SIZE.
  
 4- THERE ARE SOME SUPPLY AIR REGISTERS ON THE FIRST AND
 SECOND FLOOR THAT ARE MISSING THE DUCT SIZE AND SIZE OF
 REGISTER. PROVIDE COMPLETE INFORMATION., SEC.
 107.3.5.3(10) CITY AMENDMENTS.
  
  
 5- REMAINDER: BUILDING REVIEW WAS ALSO APPROVED ON
 01/23/18 WITH PROVISO. PROVIDE INFORMATION REQUESTED ON
 PROVISO TO AVOID CONFLICTS/DELAYS. SEE COPY OF BUILDING
 PROVISO BELOW:
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 (1)- ENERGY CALCULATIONS ARE TAKING THE CEILING FAN
 CREDIT. REVISE GREAT ROOM CEILING FAN SIZE TO COMPLY
 WITH SEC. R405.7.6 FBC-ENERGY CONSERVATION.
 (2)- SOIL TEST REPORT SUBMITTED NEEDS THE ENGINEER'S
 ORIGINAL SIGNATURE (NOT COPY). CHAPTER 471 F.S.
 (3)- PROVIDE PRODUCT APPROVAL FOR THE OVERHEAD GARAGE
 DOOR THAT MEETS THE DESIGN PRESSURES CALCULATED BY THE
 ARCHITECT ON SHEET A-301.
 (4)- DESIGNER OF RECORD TO APPROVE ABOVE PRODUCT
 APPROVAL. SEC. 107.3.4.1 CITY AMENDMENTS. NOTE: PLEASE
 PLACE THE REVIEW STAMP ON THE FRONT OF THE PRODUCT
 APPROVAL NOT ON THE BACK.
 (5)- PROVIDE SURVEY (2 COPIES) THAT MATCHES PROPOSED
 HOUSE IN LOT "B" AND THE ADDRESS 245 EDMOR RD.
  
 ****PLEASE PROVIDE RESPONSE LETTER ADDRESSING EACH
 COMMENT TO HELP EXPEDITE THE REVIEW PROCESS.
  
 ****PLEASE INSERT ANY REVISED DRAWING AND REMOVE OLD
 DRAWING. SUBMIT OLD DRAWINGS FOR REFERENCE OF ALREADY
 REVIEWED DRAWINGS. DO NOT STAPLE OLD DRAWINGS TO PLANS.
  
  