Plan Review Notes
Plan Review Notes For Permit 18080205
Permit Number 18080205
Review Stop E
Sequence Number 1
Notes
Date Text
2018-08-22 06:54:18ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AN ELECTRICAL PLAN FOR SIGN, AND SHOW
 LOCATION OF SIGNS ON BUILDING, NOT A PLAN THAT SAYS
 "L.E.D." FBC 107.2.1-NOT ENOUGH INFORMATION.
  
 2. NO DISCONNECT WITHIN SIGHT OF SIGN TO DISCONNECT ALL
 UNGROUNDED CONDUCTORS OF BRANCH CIRCUIT/FEEDER AT POINT
 WHICH CONDUCTORS ENTER SIGN AS PER 600.6A1 NEC 2014.
  
 3. ELECTRICAL SUB-PERMIT MUST BE PULLED BY LICENSED
 ELECTRICIAN, (EC) OR (ER) REGISTERED TO PALM BEACH
 COUNTY, BECAUSE NEW DISCONNECT REQUIREMENTS OF 600.6A1
 NEC AND INSTALLATION OF ASTRONOMICAL TIME CLOCK (FBC CE
 405.2.4) ARE OUT OF SCOPE FOR ES LICENSE. PLEASE SEE
 SCOPE OF AN ES LICENSE BELOW:
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
  
 HAVE QUALIFIER CALL ME IF THERE ARE ANY QUESTIONS
 PLEASE. CELL PHONE IS BEST AS I AM NORMALLY IN THE
 FIELD PERFORMING INSPECTIONS.
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  
  