| Plan Review Notes For Permit 18080200 |
| Permit Number |
18080200 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-08-29 07:15:29 | NEW DISCONNECT REQURIED (RED-LINED ON PLAN) BY 600.6A1 | | | NEC 2014 AND ASTRONOMICAL TIMECLOCK REQUIRED BY FBC CE | | | 405.2.4 TO BE INSTALLED AND PERMITTED BY LICENSED | | | ELECTRICIAN. FAILURE TO SECURE PROPER PERMIT AND THEN | | | THE INSTALLATION OF THESE ITEMS BY SIGN CONTRACTOR WILL | | | RESULT IN A 4X PERMIT FEE. |
|