| 2018-11-07 06:50:07 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. SEAL BY ENGINEER UNREADABLE AND IS NOT VALID. PHOTO |
| | COPIES OF SEALS ARE NOT ACCEPTABLE. PLEASE SEE |
| | REQUIREMENTS FOR SEALS BELOW: |
| | |
| | PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE |
| | LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE'S |
| | SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR |
| | COPIED IMAGE OF THE LICENSEE'S SIGNATURE IS NOT ALLOWED |
| | ON PHYSICALLY TRANSMITTED DOCUMENTS. |
| | CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL |
| | SIGN BY HAND AN ORIGINAL OF THE LICENSEE'S SIGNATURE ON |
| | EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE, |
| | DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE'S |
| | SIGNATURE SHALL NOT BE USED. |
| | |
| | AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED |
| | DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A |
| | WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART |
| | OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO |
| | PARTIALLY OVERLAP THE LICENSEE'S SIGNATURE SUCH THAT |
| | THE SIGNATURE IS NOT MADE ILLEGIBLE. |
| | CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN |
| | USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN |
| | EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE |
| | LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE |
| | SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE |
| | SIGNATURE ILLEGIBLE. |
| | |
| | 2. LICENSED ELECTRICIAN NEEDED TO PULL ELEC PERMIT FOR |
| | SIGN FOR REQUIRED ELECTRICAL WORK. MUST BE EC OR ER |
| | REGISTERED IN PALM BEACH COUNTY. NEW DISCONNECT |
| | REQUIRED BY 600.6A1 NEC AND BRANCH CIRCUIT REQUIRED BY |
| | 600.5 NEC OUT OF SCOPE OF WORK FOR ES LICENSE. PLEASE |
| | SEE SCOPE OF ES LICENSE BELOW: |
| | |
| | SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C. |
| | 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN |
| | SPECIALTY CONTRACTOR) |
| | |
| | THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL |
| | FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION, |
| | INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF |
| | ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF |
| | CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR |
| | ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR |
| | TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER |
| | THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE |
| | REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE |
| | BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY |
| | STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN |
| | TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250) |
| | VOLTS MAXIMUM. |
| | |
| | PROVIDE LETTER WHEN RESUBMITTING WITH PERMIT # OF |
| | PERMIT FOR ADDITIONAL ELECTRICAL WORK REQUIRED FOR SIGN |
| | INSTALLATION BY LICENSED ELECTRICIAN. |
| | |
| | HAVE QUALIFIER CALL ME IF THERE ARE ANY QUESTIONS. |
| | CONTACT INFORMATION IS BELOW. CELL PHONE IS BEST. |
| | |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE |
| | PREVIOUSLY REVIEWED SHEETS. |
| | CODES IN EFFECT: |
| | |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA |
| | BUILDING CODE 2017 6TH ED. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | V/R, |
| | |
| | FRANK GIAQUINTO III |
| | ELECTRICAL INSPECTOR |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WPB |
| | [email protected] |
| | CELL: 561-657-1653 |
| | |