2018-11-07 06:50:07ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. SEAL BY ENGINEER UNREADABLE AND IS NOT VALID. PHOTO
 COPIES OF SEALS ARE NOT ACCEPTABLE. PLEASE SEE
 REQUIREMENTS FOR SEALS BELOW:
  
 PHYSICALLY TRANSMITTED DOCUMENTS REQUIRE THAT THE
 LICENSEE CREATE BY HAND AN ORIGINAL OF THE LICENSEE'S
 SIGNATURE. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE IS NOT ALLOWED
 ON PHYSICALLY TRANSMITTED DOCUMENTS.
 CHAPTER 61G15-23.003(1), F.A.C., THE LICENSEE SHALL
 SIGN BY HAND AN ORIGINAL OF THE LICENSEE'S SIGNATURE ON
 EACH PAGE REQUIRED TO BE SEALED. A SCANNED, FACSIMILE,
 DIGITALLY CREATED OR COPIED IMAGE OF THE LICENSEE'S
 SIGNATURE SHALL NOT BE USED.
  
 AS FOR CREATING THE SEAL, PHYSICALLY TRANSMITTED
 DOCUMENTS ARE ALLOWED TO BE EMBOSSED, SEALED USING A
 WET STAMP, OR CONTAIN A DIGITALLY CREATED SEAL (AS PART
 OF THE BORDER). IN EACH OF THESE CASES THE SEAL IS TO
 PARTIALLY OVERLAP THE LICENSEE'S SIGNATURE SUCH THAT
 THE SIGNATURE IS NOT MADE ILLEGIBLE.
 CHAPTER 61G15-23.003(2), F.A.C., THE LICENSEE MUST THEN
 USE A WET SEAL, A DIGITALLY CREATED SEAL, OR AN
 EMBOSSING SEAL PLACED PARTIALLY OVERLAPPING THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. THE PLACEMENT OF THE SEAL SHALL NOT RENDER THE
 SIGNATURE ILLEGIBLE.
  
 2. LICENSED ELECTRICIAN NEEDED TO PULL ELEC PERMIT FOR
 SIGN FOR REQUIRED ELECTRICAL WORK. MUST BE EC OR ER
 REGISTERED IN PALM BEACH COUNTY. NEW DISCONNECT
 REQUIRED BY 600.6A1 NEC AND BRANCH CIRCUIT REQUIRED BY
 600.5 NEC OUT OF SCOPE OF WORK FOR ES LICENSE. PLEASE
 SEE SCOPE OF ES LICENSE BELOW:
  
 SIGN CONTRACTORS F.S. 489.505 (#19) AND F.A.C.
 61G6-7.001 SPECIALTY ELECTRICAL CONTRACTORS (#2 SIGN
 SPECIALTY CONTRACTOR)
  
 THE SCOPE OF CERTIFICATION INCLUDES THE STRUCTURAL
 FABRICATION INCLUDING CONCRETE FOUNDATION, ERECTION,
 INSTALLATION, ALTERATION, REPAIR, SERVICE AND WIRING OF
 ELECTRICAL SIGNS AND OUTLINE LIGHTING. THE SCOPE OF
 CERTIFICATION SHALL NOT INCLUDE THE PROVISION OF, OR
 ANY ELECTRICAL WORK BEYOND, THE LAST DISCONNECT MEAN OR
 TERMINAL POINTS. HOWEVER, A CONTRACTOR CERTIFIED UNDER
 THIS SECTION MAY PROVIDE THE ELECTRICAL ENTRANCE
 REQUIREMENTS FOR METERING AND MAIN DISCONNECT OF REMOTE
 BILLBOARDS OR SIGNS WHICH ARE INDEPENDENT OF ANY
 STRUCTURE OR BUILDING AND WHICH REQUIRE NO MORE THAN
 TWENTY-FIVE (25) KILOWATTS AT TWO HUNDRED FIFTY (250)
 VOLTS MAXIMUM.
  
 PROVIDE LETTER WHEN RESUBMITTING WITH PERMIT # OF
 PERMIT FOR ADDITIONAL ELECTRICAL WORK REQUIRED FOR SIGN
 INSTALLATION BY LICENSED ELECTRICIAN.
  
 HAVE QUALIFIER CALL ME IF THERE ARE ANY QUESTIONS.
 CONTACT INFORMATION IS BELOW. CELL PHONE IS BEST.
  
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE
 PREVIOUSLY REVIEWED SHEETS.
 CODES IN EFFECT:
  
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA
 BUILDING CODE 2017 6TH ED.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 V/R,
  
 FRANK GIAQUINTO III
 ELECTRICAL INSPECTOR
 ELECTRICAL PLANS EXAMINER
 CITY OF WPB
 [email protected]
 CELL: 561-657-1653
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved