| 2018-09-12 10:15:39 | APPROVED PROVISIONALLY. DO YOU KNOW WHICH WINDOW YOU |
| | ARE USING FROM THE FLORIDA PRODUCT APPROVAL NUMBER |
| | 243-R20 ? I PRESUMED IT IS 243.5. YOU DID NOT PROVIDE |
| | THE CERTIFICATE AGENCY CERTIFICATE OR INSTALLATION |
| | INSTRUCTION. I PRINTED IT FOR YOU WHICH TURNED OUT TO |
| | BE MIAMI DADE NOA 17-0614.11. I ATTACHED ONLY THE NOA |
| | TO THE PLAN AS THE FLORIDA PRODUCT APPROVAL SHEET JUST |
| | CONFUSES THE ISSUE. YOUR ENGINEER OF RECORD, ANDRE H. |
| | THOMAS IS SUPPOSED TO PROVIDE EVIDENCE THAT HE REVIEWED |
| | THE USE OF THIS PRODUCT FOR CONSISTENCY WITH THE DESIGN |
| | OTHER ISSUES THAT WERE NOT ADDRESSED IN THE RESPONSE |
| | SHOULD ALSO BE PROVIDED BY THE ENGINEER AS HE IS |
| | RESPONSIBLE FOR THE DESIGN. THOSE ITEMS ARE AS FOLLOWS: |
| | |
| | 1. [FBC EB501]PROVIDE DESIGN DATA: OCCUPANCY=R-3, LEVEL |
| | OF ALTERATION AND TYPE OF CONSTRUCTION. |
| | |
| | 2. [FBC 107.2.5]PROVIDE FURTHER DETAIL SHEET A-1 BLOCK |
| | IN-FILL. WHAT IS THE EXTERIOR FINISH, INSULATION AND |
| | INTERIOR FINISH. |
| | |
| | 3. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN |
| | EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW |
| | FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE |
| | REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE |
| | REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE |
| | R402.1.2. |
| | NEW FENESTRATION SHOULD HAVE MAXIMUM SOLAR HEAT GAIN |
| | CO-EFFICIENT (SHGC) OF 0.25 IN CLIMATE ZONE 1. |
| | |
| | THE ENGINEER MAY PROVIDE A LETTER ADDRESSING THESE |
| | ISSUES FOR MY REVIEW OR IT MAY BE GIVEN TO THE BUILDING |
| | INSPECTOR AT THE FRAMING INSPECTION. |
| | |