| 2018-08-28 08:16:48 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18080195 |
| | REVIEWED: AUGUST 28, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC EC = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. [FBC EB501]PROVIDE DESIGN DATA: OCCUPANCY=R-3, LEVEL |
| | OF ALTERATION AND TYPE OF CONSTRUCTION. |
| | |
| | 2. [FBC 107.2.5]CHANGE FIRST LINE OF GENERAL NOTES TO |
| | SAY 2017 BUILDING CODE. |
| | |
| | 3. [FBC 107.2.5]PROVIDE FURTHER DETAIL SHEET A-1 BLOCK |
| | IN-FILL. WHAT IS THE EXTERIOR FINISH, INSULATION AND |
| | INTERIOR FINISH. |
| | |
| | 4. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN |
| | EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW |
| | FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE |
| | REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE |
| | REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE |
| | R402.1.2. |
| | NEW FENESTRATION SHOULD HAVE MAXIMUM SOLAR HEAT GAIN |
| | CO-EFFICIENT (SHGC) OF 0.25 IN CLIMATE ZONE 1. |
| | |
| | 5. [FBC 107.2.5]SHEET A-2. ADJUST THE DASHED LINE OF |
| | UPPER CABINET TO ACCOUNT FOR WINDOWS AND ADD INTERIOR |
| | ELEVATION FOR CLARITY. |
| | |
| | 6. [FBC 107.2.5]REVIEW OVEN AND REFRIDGERATOR |
| | DOCUMENTATION TO MAKE SURE THEY ARE COMPATIBLE SIDE BY |
| | SIDE. |
| | |
| | 7. [FBC AMENDED 107.2.1.2]ON PRODUCT APPROVAL FOR FIXED |
| | WINDOW FL243-R20, PLEASE SELECT THE PRODUCT IN MIND, |
| | AND PRINT OUT THE CERTIFICATE AND INSTRUCTIONS FOR |
| | ATTACHMENT DETAILS. |
| | |
| | NOTE: |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |