| 2018-10-30 13:17:04 | 2ND REVIEW REV 1: |
| | PLUMBING COMMENTS: APPROVED WITH EXCEPTION |
| | |
| | 1. A REVISION IS REQUIRED REFLECTING THE CHANGES LISTED |
| | BELOW. FAILURE TO CORRECT THE LISTED DEFICIENCIES IN |
| | THIS PLAN PRIOR TO INSPECTION WILL RESULT IN FAILED |
| | INSPECTION(S) AND THE ASSESSMENT OF RE-INSPECTION |
| | FEE(S). |
| | 2. REGARDING SANITARY PLUMBING RISER ON PLAN SHEET S-1: |
| | PLEASE SEE REDLINED NOTES AND MARKUPS IN CLOUDED AREAS |
| | FOR THE ITEMS LISTED BELOW; REVISE PLAN AND SUBMIT AS A |
| | REVISION. |
| | A. MASTER BATH:FIXTURE DRAINS FOR SHOWER AND BATHTUB |
| | MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES |
| | P3108.1 |
| | B. GUEST BATH: FIXTURE DRAINS FOR TWO SHOWERS MUST |
| | CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES P3108.1 |
| | C. BATH #2: FIXTURE DRAINS FOR SHOWER AND WATER CLOSET |
| | MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES |
| | P3108.1 |
| | D. BATH #3: FIXTURE DRAINS FOR SHOWER AND WATER CLOSET |
| | MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES |
| | P3108.1 |
| | E. KITCHEN SINK: DISHWASHERS TO CONNECT TO SINK |
| | TAILPIECE ABOVE THE TRAP INLET. REVISE OR DO NOT SHOW |
| | THE DISHWASHER CONNECTIONS ON THE DRAWING. |
| | D. GENERAL NOTE: ALL FIXTURE DRAINS MUST CONNECT TO |
| | VENT IN ACCORDANCE WITH TABLE P3105.1; MAXIMUM DISTANCE |
| | OF TRAP TO VENT. |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | EMAIL: [email protected] |
| | PHONE: 561-805-6715 |
| | |
| 2018-10-25 09:47:33 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2ND REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. REGARDING SANITARY PLUMBING RISER ON PLAN SHEET S-1: |
| | PLEASE SEE REDLINED NOTES AND MARKUPS IN CLOUDED AREAS |
| | FOR THE ITEMS LISTED BELOW; REVISE PLAN AND RESUBMIT. |
| | 2017 FBC RES 3108.1 |
| | A. MASTER BATH:FIXTURE DRAINS FOR SHOWER AND BATHTUB |
| | MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES |
| | P3108.1 |
| | B. GUEST BATH: FIXTURE DRAINS FOR TWO SHOWERS MUST |
| | CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES P3108.1 |
| | C. BATH #2: FIXTURE DRAINS FOR SHOWER AND WATER CLOSET |
| | MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES |
| | P3108.1 |
| | D. BATH #3: FIXTURE DRAINS FOR SHOWER AND WATER CLOSET |
| | MUST CONNECT INDEPENDENTLY TO THE WET VENT. FBC RES |
| | P3108.1 |
| | E. KITCHEN SINK: DISHWASHERS TO CONNECT TO SINK |
| | TAILPIECE ABOVE THE TRAP INLET. REVISE OR DO NOT SHOW |
| | THE DISHWASHER CONNECTIONS ON THE DRAWING. |
| | D. GENERAL NOTE: ALL FIXTURE DRAINS MUST CONNECT TO |
| | VENT IN ACCORDANCE WITH TABLE P3105.1; MAXIMUM DISTANCE |
| | OF TRAP TO VENT. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | (STAMPED/SEALED AND SIGNED BY DESIGNER OF RECORD IN |
| | ACCORDANCE WITH FS 471 FAC 61G15) INTO THE ORIGINAL |
| | SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| | ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| | REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |