| 2018-09-07 12:39:50 | REVIEW COMPLETED BY JERALD SMITH 0017-P |
| 2018-09-06 10:47:24 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | PERMIT 18080194 |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. REGARDING SANITARY PLUMBING RISER ON PLAN SHEET S-1: |
| | A. DESIGNATION C.O. IF CLEANOUTS SHOWN AT END OF |
| | BATHROOM SANITARY RUNOUTS ON THE GROUND FLOOR ARE TO BE |
| | REQUIRED THEY MUST BE ACCESSIBLE. 2017 FBC RES |
| | 3005.2.10. PLEASE CLARIFY. |
| | |
| | B. AUTOMATIC CLOTHES WASHERS REQUIRE A FIXTURE TRAP PER |
| | 2017 FBC RES 3201.6 AND A VENT PER 2017 FBC RES 3105.1. |
| | CORRECT ON THE SANITARY RISER DIAGRAM ON PLAN SHEET S-1 |
| | TO SHOW THE SAME. |
| | |
| | C. FIXTURE DRAINS FOR SHOWER AND BATHTUB IN MASTER BATH |
| | #2 MUST CONNECT INDEPENDENTLY TO THE WET VENT. CORRECT |
| | ON THE SANITARY RISER DIAGRAM ON PLAN SHEET S-1 TO SHOW |
| | THE SAME. 2017 FBC RES 3108.1 |
| | |
| | D. WHAT IS THE TERM "STUTTER VENT" NOTED AT DIFFERENT |
| | FIXTURES ON RISER DIAGRAM? PLEASE CLARIFY. |
| | |
| | E. PLEASE CLARIFY 3" VTR RISING ABOVE 2" WET VENTS. |
| | |
| | 2. THERE IS A GAS FIRED TANKLESS WATER HEATER AND A BBQ |
| | GRILL NOTED ON PLAN SHEET A-201. A GAS PLAN HAS NOT |
| | BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. A GAS PLAN |
| | REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. A SEPARATE |
| | GAS PERMIT AND PLANS WILL BE REQUIRED FOR A CONTRACTOR |
| | TO PERFORM THE RELATED WORK PER WPB AMEND. TO FBC SEC. |
| | 105.1. PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT |
| | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE |
| | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE |
| | FBC-R, SEC. G2404.3. |
| | A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS |
| | INSTALLATION OR MODIFICATION OF SYSTEM. |
| | |
| | 3. NOTE: SEE FOLLOWING COMMENTS |
| | A. HAND HELD SHOWER REQUIRES AN ATMOSPHERIC VACUUM |
| | BREAKER AT SHOWER ARM OUTLET. 2017 FBC RES 2708.5 |
| | |
| | B. SHOWER CONTROL VALVE(S) SHALL BE PRESSURE BALANCED |
| | PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE |
| | TYPES WITH HIGH TEMPERATURE LIMITING STOP. 2017 FBC RES |
| | 2708.4 |
| | |
| | C. ACCESSIBLE TEMPERATURE LIMITING DEVICE REQUIRED ON |
| | HOT WATER TO MASTER BATH BATHTUB(S) IS REQUIRED. 2017 |
| | FBC RES 2713.3 |
| | |
| | D. THE VALVES FOR THE STACKABLE WASHING MACHINE(S) |
| | SHALL BE ACCESSIBLE. 2017 FBC RES P2903.9.3 |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |