| 2018-10-25 08:43:10 | A GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL |
| | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT |
| | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE |
| | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. |
| | PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT |
| | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE |
| | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. |
| | 107.2.1. |
| | GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE |
| | FBC-R, SEC. G2404.3. |
| | GAS APPLIANCES SHALL BE LISTED AND LABELED PER FBC-FUEL |
| | GAS SEC. 301.3. |
| | A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS |
| | INSTALLATION OR MODIFICATION OF SYSTEM. |
| | IF THERE IS AN EXISTING SYSTEM, THE BTU LOAD OF THE |
| | EXISTING GAS SYSTEM MUST BE ADDED INTO THE TOTAL BTU |
| | LOAD ON THE SYSTEM TO ENSURE THE EXISTING SYSTEM IS |
| | PROPERLY SIZED. IF UNDERSIZED, THE EXISTING SYSTEM MUST |
| | BE REDONE TO ENSURE A SAFE OPERATING SYSTEM. SUBMIT A |
| | GAS PIPING RISER DIAGRAM THAT SHOWS THE TYPE OF |
| | EXISTING APPLIANCE, THE BTU LOAD OF EACH APPLIANCE, THE |
| | PIPE SIZE AND TYPE OF PIPE TO EACH APPLIANCE, AND THE |
| | DISTANCE OF THE LONGEST LENGTH OF PIPING FROM THE POINT |
| | OF DELIVERY TO THE MOST REMOTE OUTLET AND THE LOAD OF |
| | THE SECTION. NOTE: IF THE EXISTING SYSTEM IS LESS THAN |
| | A 2 PSI SYSTEM AND THE SYSTEM PRESSURE IS INCREASED TO |
| | 2 PSI, A LINE PRESSURE REGULATOR IS REQUIRED AT ALL THE |
| | EXISTING APPLIANCES. FBCR SECS.G2412.4, G2412.8, |
| | G2413.1, G2413.2, G2413.3. |
| | |
| | |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6715 |