2018-08-27 11:27:14CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH
 PANEL INCLUDING INFORMATION FROM THE POWER COMPANY
 STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR
 THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE
 SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE.
 NEC 110.9, 110.10; FBC RE E3603.3
 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC
 210.8(D); FBC RE E3902.10
 3. RISER DIAGRAM SHOWS A DIFFERENT CONFIGURATION THAN
 THE ELECTRICAL PLAN. WILL THERE BE MAIN BREAKER PANELS
 ON THE OUTSIDE OF THE GARAGE THAT FEED INTERIOR MAIN
 LUG PANELS? OR WILL THERE BE MAIN BREAKER PANELS IN THE
 GARAGE? THE PANEL SCHEDULES FOR BOTH PANELS SHOWS THEM
 AS MAIN LUG ONLY. CORRECT DISCREPANCY. IF THERE ARE
 MAIN LUG PANELS IN THE GARAGE, THESE WILL REQUIRE AN
 EQUIPMENT GROUNDING CONDUCTOR(EGC). IF THE METER FEEDS
 DIRECTLY TO A MAIN BREAKER PANEL, THIS SHOULD NOT HAVE
 AND EGC. PROVIDE CORRECTIONS. WPB FBC 107.2.1; NEC
 250.6, 250.122; FBC RE E3610.4, E3704.6, E3607.3.1
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  