| 2018-08-27 11:27:14 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| | FS = FLORIDA STATUTES |
| | |
| | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| | |
| | 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR EACH |
| | PANEL INCLUDING INFORMATION FROM THE POWER COMPANY |
| | STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| | THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| | SERVICE EQUIPMENT AND DOWNSTREAM PANELS IS ADEQUATE. |
| | NEC 110.9, 110.10; FBC RE E3603.3 |
| | 2. PROVIDE GFCI PROTECTION FOR DISHWASHER. NEC |
| | 210.8(D); FBC RE E3902.10 |
| | 3. RISER DIAGRAM SHOWS A DIFFERENT CONFIGURATION THAN |
| | THE ELECTRICAL PLAN. WILL THERE BE MAIN BREAKER PANELS |
| | ON THE OUTSIDE OF THE GARAGE THAT FEED INTERIOR MAIN |
| | LUG PANELS? OR WILL THERE BE MAIN BREAKER PANELS IN THE |
| | GARAGE? THE PANEL SCHEDULES FOR BOTH PANELS SHOWS THEM |
| | AS MAIN LUG ONLY. CORRECT DISCREPANCY. IF THERE ARE |
| | MAIN LUG PANELS IN THE GARAGE, THESE WILL REQUIRE AN |
| | EQUIPMENT GROUNDING CONDUCTOR(EGC). IF THE METER FEEDS |
| | DIRECTLY TO A MAIN BREAKER PANEL, THIS SHOULD NOT HAVE |
| | AND EGC. PROVIDE CORRECTIONS. WPB FBC 107.2.1; NEC |
| | 250.6, 250.122; FBC RE E3610.4, E3704.6, E3607.3.1 |
| | |
| | END OF COMMENTS. |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD |
| | SHEETS?. |
| | |