2018-09-11 15:35:39PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE PLANS HAVE SEVERAL REFERENCES TO THE FBC FIFTH
 EDITION (2014). THE FBC SIXTH EDITION (2017) WENT INTO
 EFFECT ON JANUARY 1, 2018. ALL NEW PERMITS APPLIED FOR
 ON OR AFTER THAT DATE ARE REQUIRED TO COMPLY WITH AND
 REFERENCE THE FBC SIXTH EDITION (2017). FS CHAPTER 553
  
 2) THE REFERENCED STANDARDS ON SHEET A-101 ARE OLD AND
 NOT THE ONES THAT ARE LISTED IN CHAPTER 46 OF THE 2017
 FBC RESIDENTIAL.
  
 3) ON A-201 THE GARAGE SEPARTION CODE SECTIONS THAT ARE
 SPECIFIED ARE INCORRECT. FBC-R 302.5 IS THE APPLICABLE
 CODE IN THE 2017 EDITION. FBC 107.2.1
  
 4) ON SHEETS A-201 AND A-202, TYPICAL RAILING NOTE #3,
 R312.1.3 NO LONGER HAS THE PART ABOUT THE 64 SQUARE
 INCHES. FBC 107.2.1
  
 5) ON SHEETS A-201 AND A-202, TYPICAL STAIR NOTES NEED
 TO BE UPDATED TO THE 2017 FBC. NOTE #3 ABOUT THE SUM OF
 TWO RISERS AND ONE TREAD IS NO LONGER IN THE CODE.
 FBC-R 311.7.5
  
 6) ON SHEETS A-201 AND A-202, UPDATE THE EGRESS NOTE TO
 CODE SECTIONS 311.2, 311.3.1 AND 310.2.2. NOTE 2 SHOULD
 READ THAT SILL HEIGHT OF NOT MORE THAN 44".
  
 7) UP DATE THE STAIR NOTES ON A-201 AND A-202 TO 2017
 FBC-R TABLE R301.5 FOR MINIMUM UNIFORMLY DISTRUBITED
 LIVE LOADS.
  
 8) THE ELEVATIONS ON THE THE DRAINAGE PLAN SHEET C-1
 ARE IN NGVD-29. ON OCTOBER 5TH, 2017, THE CITY OF WEST
 PALM BEACH ADOPTED NEW FLOOD INSURANCE RATE MAPS WHICH
 USE NAVD 88 AS THE VERTICAL DATUM.
  
 9) SUBMIT THE MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE OUTDOOR GAS COOKTOP
 AND EXHAUST HOOD. FBC 107.2.1
  
 10) ON SHEETS S-2 AND S-3 THE ROOF FRAMING NOTES
 SPECIFY EXPOSURE D AND THE BEAM UPLIFT CALCULATIONS
 SPECIFY EXPOSURE C. PLEASE COORDINATE THE EXPOSURE
 CATEGORY. FBC-R301.2.1.4.3
  
 11) THE WIND DESIGN PRESSURES FOR THE WINDOWS AND DOORS
 ON SHEET A-301 ARE DIFFERENT FROM THE ONES ON SHEETS
 S-2 AND S-3. PLEASE REVIEW AND REVISE AS NEEDED.
 FBC-R301.2.1 AND ASCE 7-10.
  
 12) ON SHEET A-301 THE NOA NO. FOR THE SECTIONAL GARAGE
 DOOR DOES NOT MATCH THE ONE THAT WASA SUBMITTED.
  
 13) SECTION 2 ON SHEET A-401 HAS A NOTE STATING
 CONCRETE TILE OVER 30# FELT. THE 30# FELT ALONE IS NOT
 AN ACCEPTABLE UNDERLAYMENT FOR CONCRETE TILE. SPECIFY
 AN APPROVED CONCRETE ROOF TILE UNDERLAYMENT AND
 ASSEMBLY. FBC-R905.3
  
 14) SPECIFY THE METHOD OF ATTACHMENT THAT WILL BE USED
 TO INSTALL THE CEMENT ROOF TILE. IF AN ADHESIVE OR
 MORTAR WILL BE USED, THEN SUBMIT TWO SETS OF PRODUCT
 APPROVALS FOR IT. FBC 107.2.1 & FAC 61G20-3.001 PER
 FLORIDA STATUTE 553.842 (5)
  
 15) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE TARCO
 ROOF MEMBRANE SHOWN IN SECTION 2 ON SHEET A-401. FAC
 61G20-3.001 PER FLORIDA STATUTE 553.842 (5)
  
 16) SUBMIT TWO SETS OF THE PRODUCT APPROVALS,
 MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE SEALOFLEX WATERPROOFING SYATEM.
 FBC 107.2.1, FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5) AND FBC-R905.15
  
 17) PRODUCT APPROVALS FOR SINGLE HUNG WINDOWS, NOA NO.
 16-1003.01, WERE SUBMITTED AND THERE ARE NONE SHOWN OR
 SPECIFIED ON THE PLANS. PLEASE REMOVE THEM AS THEY DO
 NOT APPLY TO THIS PROJECT. FBC 107.2.1
  
 18) REVISE THE WINDOW SCHEDULE ON SHEET A-302 TO
 PROVIDE A MORE ACQURATE MATCH WITH THE PLANS. FBC
 107.2.1
  
 19) REVIEW THE PRODUCT APPROVAL NUMBERS ON THE DOOR
 SCHEDULE AND REVISE THEM TO MATCH THE ONES THAT ARE
 BEING SUBMITTED. FBC 107.2.1
  
 20) NOA NO. 14-0908.18 FOR THE FIXED WINDOWS IS
 EXPIRED. THE INSTALLATION DRAWINGS ARE TOO SMALL TO BE
 LEGIBLE. PRINT THESE IN LANDSCAPE ORIENTATION SO THEY
 BETTER FIT THE PRINTER PAPER SIZE.
  
 21) NOA NOS. 14-0908.02 FOR THE SLIDING GLASS DOORS AND
 14-0908.07 FOR THE FRENCH DOORS EXPIRED PRIOR TO THE
 DATE OF YOUR PERMIT APPLICATION. SUBMIT CURRENT PRODUCT
 APPROVALS. FAC 61G20-3.001 PER FLORIDA STATUTE 553.842
 (5)
  
 22) SPECIFY THE DOOR THAT FL 15187.3 IS INTENDED FOR.
 FBC 107.2.1
  
 23) SUBMIT TWO SETS OF PRODUCT APPROVALS FOR THE 3'-6"
 X 8'-0" ENTRY DOOR. FAC 61G20-3.001 PER FLORIDA STATUTE
 553.842 (5)
  
 24) THE ENERGY CALCULATIONS SPECIFY A METAL ROOF AND
 THIS BUILDING HAS A CONCRETE TILE ROOF. PLEASE CORRECT.
 FBC-R101.5.1.1.2
  
 25) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  
  