Plan Review Notes
Plan Review Notes For Permit 18080193
Permit Number 18080193
Review Stop P
Sequence Number 1
Notes
Date Text
2018-09-07 12:37:34REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-06 09:32:461ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18080193
 PLUMBING COMMENTS: DENIED
  
 1. REGARDING SANITARY PLUMBING RISER ON PLAN SHEET S-1:
 A. PLEASE ID BATHROOMS ON RISER DIAGRAM, MATCHING THEM
 TO THE BATHROOMS ON PLAN SHEET A-201 AND A-202; PROVIDE
 DISTINCTIVE ID, I.E. BATH #1, BATH #2. NOTE THAT "PWDR"
 ON PLAN SHEET A-201 APPEARS TO BE "CABANA" ON THE RISER
 DIAGRAM. PLEASE CLARIFY.
  
 B. SHOWER BATH ADJACENT TO "PWDR" BATH ON PLAN SHEET
 A-201 SHOWS TWO INDIVIDUAL SHOWER DRAINS. PLUMBING
 RISER ON PLAN SHEET S-1 SHOWS ONLY ONE FIXTURE DRAIN.
 SHOW SECOND FIXTURE DRAIN FOR THE SECOND SHOWER DRAIN
 AND CONNECT TO THE WET VENT. 2017 FBC RES 3108.1
  
 C. FIXTURE DRAINS FOR SHOWERS AND WATER CLOSETS IN BOTH
 UPSTAIRS SHOWER BATHS MUST CONNECT INDEPENDENTLY TO THE
 WET VENT. CORRECT ON THE SANITARY RISER DIAGRAM ON PLAN
 SHEET S-1 TO SHOW THE SAME. 2017 FBC RES 3108.1
  
 2. THERE IS A GAS FIRED TANKLESS WATER HEATER AND A BBQ
 GRILL NOTED ON PLAN SHEET A-201. A GAS PLAN HAS NOT
 BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. A GAS PLAN
 REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. A SEPARATE
 GAS PERMIT AND PLANS WILL BE REQUIRED FOR A CONTRACTOR
 TO PERFORM THE RELATED WORK PER WPB AMEND. TO FBC SEC.
 105.1. PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1.
 GAS APPLIANCES SHALL BE LISTED AND LABELED PER THE
 FBC-R, SEC. G2404.3.
 A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
 3. NOTE: SEE FOLLOWING COMMENTS
 A. HAND HELD SHOWER REQUIRES AN ATMOSPHERIC VACUUM
 BREAKER AT SHOWER ARM OUTLET FBC RES 2708.5
  
 B. SHOWER CONTROL VALVE(S) SHALL BE PRESSURE BALANCED
 PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE
 TYPES WITH HIGH TEMPERATURE LIMITING STOP FBC RES
 2708.4
  
 C. ACCESSIBLE TEMPERATURE LIMITING CONTROL DEVICE
 REQUIRED ON HOT WATER TO BATHTUB IS REQUIRED. FBC RES
 2713.3
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711