| 2018-08-09 15:19:23 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18080156 | | | REVIEWED: AUGUST 9, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. PROVIDE +/- PRESSURES FOR EACH OPENING. | | | | | | 2. WHAT IS THE MAXIMUM OCCUPANCY OF THE ENTRY DOOR | | | SERVED? | | | | | | 3. THE PRODUCT APPROVAL IS FOR OUTSWING DOOR. PLAN SHOW | | | INSWING. PLEASE ADJUST OR PROVIDE FOR INSWING DOORS. | | | | | | 4. OTHER THAN THE REBAR INTO FOUNDATION, HOW DO THE NEW | | | COLUMNS AND HEADER BEAMS CONNECT TO EXISTING? | | | | | | 5. WHAT IS THE EXISTING WALL MATERIAL ADJACENT TO | | | OPENING? | | | | | | NOTE: | | | ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | |
|