| Plan Review Notes For Permit 18080127 |
| Permit Number |
18080127 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-10-25 09:48:57 | PLAN | | | REVIEW COMMENTS | | | | | | 2ND REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) THE FLOOR PLAN AND PARTIAL ELEVATION ON SHEET AME-1 | | | SPECIFIES A NEW IMPACT RESISTANT SINGLE HUNG WINDOW NOA | | | #17-0918.09. THE NOA NO. 17-0918.09 THAT IS ATTACHED TO | | | THE PLANS IS FOR A CGI HORIZONTAL SLIDING WINDOW. THE | | | TYPICAL WALL SECTION ON SHEET AME-1 SPECIFIES A NEW | | | IMPACTRATED SINGLE HUNG WINDOW NOA NO. 18-0124.06. | | | PLEASE CORRECT THE DRAWINGS AND PROVIDE TWO SETS OF THE | | | PRODUCT APPROVALS FOR THE PROPOSED WINDOW THAT HAVE | | | BEEN REVIEWED AND APPROVED BY THE DESIGNER OF RECORD. | | | FBC 107.3.4 | | | | | | 2) FBC 404.1.6 REQUIRES THE TOP OF THE MONOLITHIC SLAB | | | TO BE A MINIMUM OF 4" ABOVE THE ADJACENT FINISH GRADE. | | | | | | 3) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. |
|