| Plan Review Notes For Permit 18080120 |
| Permit Number |
18080120 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-10-23 10:42:12 | 10/23/18 TALKED TO ROBERT P. BROWN (OWNER) | | | (786)443-0766. HE AGREED ON GETTING PERMIT WITH PROVISO | | | INSTEAD OF GETTING PLANS REVISED NOW. REVISION FEES | | | WILL APPLY. | | | | | | | | | BUILDING REVIEW APPROVED WITH PROVISO: | | | 1- ROOF VENTS SHOWN ON PROPOSED ROOF PLAN ON SHEET S-2 | | | DON'T PROVIDE THE NET FREE CROSS VENTILATION OF 1/150 | | | AS REQUIRED BY SEC. R806.2 FBC-RESIDENTIAL. ENGINEER OF | | | RECORD TO REVISE ROOF VENTS AS REQ'D TO COMPLY. PROVIDE | | | CALCULATIONS AND REVISE LOCATION OF VENTS. | | | | | | 2- CONTRACTOR TO COMPLETE A SEPARATE SUB- PERMIT | | | APPLICATION FOR THE ROOFING WORK USING THIS PERMIT | | | #158080120 AS THE PRIMARY PERMIT. | | | | | | NOTE: | | | FOR YOUR INFORMATION ANY OTHER WORK LIKE ELECTRICAL, | | | PLUMBING, MECHANICAL, ETC. REQUIRES SEPARATE PLANS AND | | | PERMITS |
|