2018-10-23 10:42:1210/23/18 TALKED TO ROBERT P. BROWN (OWNER)
 (786)443-0766. HE AGREED ON GETTING PERMIT WITH PROVISO
 INSTEAD OF GETTING PLANS REVISED NOW. REVISION FEES
 WILL APPLY.
  
  
 BUILDING REVIEW APPROVED WITH PROVISO:
 1- ROOF VENTS SHOWN ON PROPOSED ROOF PLAN ON SHEET S-2
 DON'T PROVIDE THE NET FREE CROSS VENTILATION OF 1/150
 AS REQUIRED BY SEC. R806.2 FBC-RESIDENTIAL. ENGINEER OF
 RECORD TO REVISE ROOF VENTS AS REQ'D TO COMPLY. PROVIDE
 CALCULATIONS AND REVISE LOCATION OF VENTS.
  
 2- CONTRACTOR TO COMPLETE A SEPARATE SUB- PERMIT
 APPLICATION FOR THE ROOFING WORK USING THIS PERMIT
 #158080120 AS THE PRIMARY PERMIT.
  
 NOTE:
 FOR YOUR INFORMATION ANY OTHER WORK LIKE ELECTRICAL,
 PLUMBING, MECHANICAL, ETC. REQUIRES SEPARATE PLANS AND
 PERMITS