Plan Review Notes
Plan Review Notes For Permit 18080119
Permit Number 18080119
Review Stop P
Sequence Number 1
Notes
Date Text
2018-09-07 13:07:50REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-04 16:38:231ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18080119
 PLUMBING COMMENTS: APPROVED; SEE NOTES ON PLAN WHICH
 ARE ALSO NOTED BELOW
  
 1. HAND HELD SHOWER REQUIRES AN ATMOSPHERIC VACUUM
 BREAKER AT SHOWER ARM OUTLET FBC RES 2708.5
 2. SHOWER CONTROL VALVE(S) SHALL BE PRESSURE BALANCED
 PB,THERMOSTATIC MIXING (TM) OR COMBINATION PB/TM VALVE
 TYPES WITH HIGH TEMPERATURE LIMITING STOP FBC RES
 2708.4
 3. ACCESSIBLE TEMPERATURE LIMITING CONTROL DEVICE
 REQUIRED ON HOT WATER TO BATHTUB IS REQUIRED. FBC RES
 2713.3
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711