Plan Review Notes
Plan Review Notes For Permit 18080119
Permit Number 18080119
Review Stop E
Sequence Number 1
Notes
Date Text
2018-08-27 10:38:21CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE
 FS = FLORIDA STATUTES
  
 ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW.
  
 1. ELECTRICAL PLAN IS REQUIRED TO BE SIGNED BY PERSON
 RESPONSIBLE FOR THE DESIGN. PROVIDE CORRECTION. FS
 481.229; WPB FBC 107.2.1, 107.3.5.1.2
 2. ALL RECEPTACLE OUTLETS IN BATHROOM REQUIRE GFCI
 PROTECTION. PROVIDE CORRECTION. NEC 210.8; FBC RE
 E3902.1
 3. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE
 SUITABLE FOR DAMP LOCATIONS. NO PARTS OF CORD-CONNECTED
 LUMINAIRES, CHAIN-, CABLE-, OR CORD-SUSPENDED
 LUMINAIRES, LIGHTING TRACK, PENDANTS, OR
 CEILING-SUSPENDED (PADDLE) FANS SHALL BE LOCATED WITHIN
 A ZONE MEASURED 3 FEET HORIZONTALLY AND 8 FEET
 VERTICALLY FROM THE TOP OF THE BATHTUB RIM OR SHOWER
 STALL THRESHOLD. PROVIDE CORRECTION. NEC 410.10(D); FBC
 RE E4003.11; NEC 410.10(D); FBC RE E4003.11
 4. PROVIDE PANEL SCHEDULE INDICATING ANY NEW OR ALTERED
 CIRCUITS, THE WIRE AND BREAKER SIZE FOR THESE CIRCUITS,
 AND AFCI OR GFCI PROTECTION WHERE APPLICABLE TO COMPLY
 WITH CODE. NEC 210.8, 210.12, 210.19, 210.20, 215.5,
 408.4; WPB FBC 107.3.5; FBC RE E3706.2, E3902
 5. IF ANY ADDITIONAL LOADS ARE BEING ADDED, PROVIDE
 LOAD CALCULATION FOR SERVICE, INCLUDE EXISTING AND NEW
 LOADS TO CONFIRM CAPACITY OF SERVICE IS ADEQUATE. NEC
 215.2, 220, 408.30; FBC RE E3602.2
 6. PROVIDE SMOKE/CO ALARMS IN EACH LOCATION REQUIRED
 PER CODE. PROVIDE FULL FLOOR PLAN SHOWING ALL EXISTING
 ALARMS. IF NONE ARE EXISTING OR NOT TO CODE, SHOW AS
 NEW INSTALLATIONS. FBC RE R314.3, R315.1; WPB FBC
 107.2.1
 7. PROVIDE TAMPER RESISTANT RECEPTACLES PER CODE. A
 NOTE WILL SUFFICE. NEC 406.12; FBC RE E4002.14
  
 END OF COMMENTS.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED ?OLD
 SHEETS?.
  