Plan Review Notes
Plan Review Notes For Permit 18080100
Permit Number 18080100
Review Stop G
Sequence Number 1
Notes
Date Text
2018-09-07 12:30:08REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-04 14:43:311ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18080100
 GAS COMMENTS: DENIED
  
 1. A REVIEW OF THE LAST PERMITTED GAS WORK FOR THIS
 RESIDENCE NOTES A GAS CLOTHES DRYER WHICH IS NOT NOTED
 ON THE APPLICATION. IT DOES NOT HOWEVER NOTE THE
 EXISTING POOL HEATER SHOWN ON THE APPLICATION. THE POOL
 HEATER NEEDS TO BE PERMITTED AND INSPECTED IN
 ACCORDANCE WITH WPB AMENDMENTS TO FBC 105.1 AND 110.1.
 POOL HEATER EXHAUST NOT TO BE LOCATED WITHIN 4?-0? OF
 ANY DOOR, WINDOW OR GRAVITY INLET INTO A DWELLING AND
 DISCHARGE AWAY FROM SAID OPENING. FBC RES 1804.2.6
  
 2. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT INCLUDES
 AND SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD
 OF EACH APPLIANCE, THE PIPE SIZE, MATERIAL , AND THE
 CORRESPONDING EHD NUMBER OF THE CORRUGATED STAINLESS
 STEEL TUBING (IF APPLICABLE) FOR EACH PIPE SIZE (WPB
 AMENDMENTS TO FBC SEC.107.2.1), CLEARLY SHOWING THE
 LENGTH OF ALL CUT SECTIONS OF PIPE AND TYPE OF PIPE TO
 EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH
 OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. INDICATE EXISTING
 AND NEW PIPING AND APPLIANCES. NOTE: THE EXISTING
 SYSTEM IS A 2 PSI SYSTEM; A MP (STEP-DOWN) REGULATOR
 AND LISTED SHUTOFF VALVE INSTALLED IMMEDIATELY AHEAD OF
 EACH MP REGULATOR IS REQUIRED AT ALL APPLIANCES. FGC
 SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR
 SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3,
 G2413.4.1, G2413.4.2.
 A) A COPY OF PREVIOUS APPROVED DRAWING (3 PAGES) IS
 FURNISHED FOR YOUR USE
  
 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. WPB
 AMENDMENTS TO FBC SEC. 107.2.1.
  
 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL
 BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS
 SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37)
 OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES
 G2413.4 (1 ) THROUGH G2413.4 (21).
  
 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3
 THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS /
 INSTALLATION MANUAL FOR ALL ADDED GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND
 FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017
 FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED
 AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS
 APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF
 INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1.
  
 7. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
  
 8. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS
 AND LISTED SHUTOFF VALVE INSTALLED IMMEDIATELY AHEAD OF
 EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4,
 FBC-RESIDENTIAL SEC. G 2420.4.
  
 9. ) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC.
 G2421.1.
  
 NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS
 TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE
 GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS.
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711