| 2018-09-07 12:30:08 | REVIEW COMPLETED BY JERALD SMITH 0017-P |
| 2018-09-04 14:43:31 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | PERMIT 18080100 |
| | GAS COMMENTS: DENIED |
| | |
| | 1. A REVIEW OF THE LAST PERMITTED GAS WORK FOR THIS |
| | RESIDENCE NOTES A GAS CLOTHES DRYER WHICH IS NOT NOTED |
| | ON THE APPLICATION. IT DOES NOT HOWEVER NOTE THE |
| | EXISTING POOL HEATER SHOWN ON THE APPLICATION. THE POOL |
| | HEATER NEEDS TO BE PERMITTED AND INSPECTED IN |
| | ACCORDANCE WITH WPB AMENDMENTS TO FBC 105.1 AND 110.1. |
| | POOL HEATER EXHAUST NOT TO BE LOCATED WITHIN 4?-0? OF |
| | ANY DOOR, WINDOW OR GRAVITY INLET INTO A DWELLING AND |
| | DISCHARGE AWAY FROM SAID OPENING. FBC RES 1804.2.6 |
| | |
| | 2. THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT INCLUDES |
| | AND SHOWS THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD |
| | OF EACH APPLIANCE, THE PIPE SIZE, MATERIAL , AND THE |
| | CORRESPONDING EHD NUMBER OF THE CORRUGATED STAINLESS |
| | STEEL TUBING (IF APPLICABLE) FOR EACH PIPE SIZE (WPB |
| | AMENDMENTS TO FBC SEC.107.2.1), CLEARLY SHOWING THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE AND TYPE OF PIPE TO |
| | EACH APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH |
| | OF PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. INDICATE EXISTING |
| | AND NEW PIPING AND APPLIANCES. NOTE: THE EXISTING |
| | SYSTEM IS A 2 PSI SYSTEM; A MP (STEP-DOWN) REGULATOR |
| | AND LISTED SHUTOFF VALVE INSTALLED IMMEDIATELY AHEAD OF |
| | EACH MP REGULATOR IS REQUIRED AT ALL APPLIANCES. FGC |
| | SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3, |
| | G2413.4.1, G2413.4.2. |
| | A) A COPY OF PREVIOUS APPROVED DRAWING (3 PAGES) IS |
| | FURNISHED FOR YOUR USE |
| | |
| | 3. TYPE OF GAS (LP OR NATURAL).WPB AMEND. WPB |
| | AMENDMENTS TO FBC SEC. 107.2.1. |
| | |
| | 4. LIST THE BTU LOAD OF EACH APPLIANCE AND THE TOTAL |
| | BTU LOAD ON THE SYSTEM. REFER TO THE 2017 FBC-FUEL GAS |
| | SECS.401.8, 402.2, AND TABLES 402.4 (1) THRU 402.4 (37) |
| | OR 2017 FBC-RES. SEC. G2413.3, G2413.4 AND TABLES |
| | G2413.4 (1 ) THROUGH G2413.4 (21). |
| | |
| | 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM |
| | ON THE PLAN PER 2017 FBC-FUEL GAS SEC.402.1, 402.4.3 |
| | THRU 402.6 OR 2017 FBC RES. SEC. G2413.2, G2413.4.3. |
| | |
| | 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL ADDED GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION. FGC SEC.305.1, FBC-RES. SEC.G2408.1. |
| | |
| | 7. SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES |
| | USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE |
| | PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM |
| | THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE |
| | DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL |
| | GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1) |
| | THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8, |
| | G2413.1, G2413.2, & G2413.3. |
| | |
| | 8. SHOW THE LOCATION OF ALL MP (STEP-DOWN) REGULATORS |
| | AND LISTED SHUTOFF VALVE INSTALLED IMMEDIATELY AHEAD OF |
| | EACH MP REGULATOR. 2017 FBC-FUEL GAS SEC.409.4, |
| | FBC-RESIDENTIAL SEC. G 2420.4. |
| | |
| | 9. ) SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE |
| | PRESSURE REGULATORS. REGULATORS INSTALLED ON THE |
| | EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR |
| | INSTALLATION. 2014 FGC SEC.410.1, 2017 FBC-RES. SEC. |
| | G2421.1. |
| | |
| | NOTE - A COMPREHENSIVE REVIEW COULD NOT BE DONE AT THIS |
| | TIME AND ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| | GENERATED UPON THE RE-REVIEW OF SUBMITTED CORRECTIONS. |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |