| 2018-09-18 07:59:17 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. SHT. A-0.0.02 THE PLUMBING FIXTURE COUNT BREAKDOWN |
| | IS REFERENCING THE TENNIS CLUBHOUSE PLEASE CLARIFY. PER |
| | WPB AMEND TO FBC 107.2.1 |
| | |
| | 2. SHT. A-0.0.02 THE PLUMBING FIXTURE COUNT BREAKDOWN |
| | IS OVERLAPPING THE BUILDING HEIGHT DATA AND IS |
| | ILLEGIBLE PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 3. SHT. A -0.0.02 THE BUILDING OCCUPANCY IS MISSING THE |
| | NUMBER OF PEOPLE PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 4. SHT. A-4.1.02 DETAILS # 2,3,10 KEY # 1,2 HAVE |
| | PRINTING OVER THE TOP OF THEM RENDERING THEM ILLEGIBLE |
| | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 5. SHT. A-7.0.01 THE TEXT, LABELS AND DIMENSIONS ARE TO |
| | LIGHT READ PLEASE DARKEN . PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 6. SHT. P-3.0.00 + P-1.4.01 THE MOP SINK IS NOT VENTED |
| | SHALL COMPLY WITH FBC PL 901.2.1 |
| | |
| | 7. SHT. P-4.0.00 DETAIL #4 SHOWS A HUB DRAIN IT IS NOT |
| | SHOWN ON THE FLOOR PLAN OR ISOMETRIC PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 8. SHT. P-4.0.00 DETAIL #6 SHOWS SHOCK ARRESTORS PLEASE |
| | SHOW LOCATION ON WATER ISOMETRIC. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 9. SHT. P-4.0.00 DETAIL #4 SHOW SIZE OF EXPANSION TANK. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 10. PROVIDE A PLUMBING FIXTURE BREAK DOWN TO SHOW WHY |
| | THE MENS FIXTURE COUNT IS HIGHER THAN THE WOMENS SHALL |
| | COMPLY WITH FBC PL TABLE 403.1 AND SEC 403.1.1 |
| | |
| | 11. PROVIDE A SITE PLAN SHOWING THE WATER METER AND |
| | BACK FLOW. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 12. PLEASE PROVIDE APPROVAL FOR THE RELOCATED FUEL TANK |
| | FROM PALM BEACH COUNTY DEPARTMENT OF ENVIRONMENTAL |
| | RESOURCES. |
| | |
| | 13. PROVIDE DOCUMENTATION DECLARING THE CALCIFICATION |
| | OF THE LIQUID FUELS AND CHEMICALS. PER WPB AMEND TO FBC |
| | 107.2.1. EDITIONAL INFORMATION NEEDED |
| | |
| | 14. PROVIDE MSDS SHEETS FOR THE FERTILIZERS, CHEMICALS |
| | AND FUELS BEING USED ON THIS PROPERTY. PER WPB AMEND TO |
| | FBC 107.2.1 |
| | |
| | 15. PLEASE PROVIDE THE AMOUNTS, HOW THERE BEING STORED |
| | AND EXACT LOCATION OF ALL FERTILIZERS, CHEMICALS AND |
| | FUELS BEING USED ON THIS PROPERTY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 16. SHOW COMPLIANCE ON THE PLAN WITH NFPA 30 AND 101 |
| | |
| | 17. PROVIDE PLUMBING PLAN AND ISOMETRIC FOR ALL PIPING |
| | IN THE COVERED EQUIPMENT AREA AND FUEL STORAGE ALSO THE |
| | FERTILIZER STORAGE BUILDING. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | |
| | 18. PROVIDE MANUFACTURE SPECIFICATIONS FOR ALL |
| | EQUIPMENT. PER WPB AMEND TO FBC 107.2.1 |
| | |
| | 19. A SAND OIL SEPARATOR IS REQUIRED FOR DRAINS FROM |
| | COVERED EQUIPMENT BUILDING. FBC PL 1003.4 |
| | |
| | 20. SHT A-1.4.03 SHOWS COMPRESSED AIR PLEASE PROVIDE A |
| | FLOOR PLAN AND RISER DIAGRAM SHOW PIPING TYPE AND SIZE. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |