Plan Review Notes
Plan Review Notes For Permit 18080050
Permit Number 18080050
Review Stop G
Sequence Number 1
Notes
Date Text
2018-08-09 08:08:101) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. WPB AMEND.
 TO FBC SEC. 107.2.1.
 2) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL GAS
 EQUIPMENT. ALL EQUIPMENT SHALL BE LISTED AND
 LABELED.2017 FBC-FUEL GAS SEC.301.3.
 3) THIS GAS PERMIT CANNNOT BE ISSUED UNTIL THE MASTER
 PERMIT #18050859 IS ISSUED.
 4) A SEPARATE PERRMIT WILL BE REQUIRED FOR THE
 INSTALLATION OF THE LP TANKS AND PIPING WHICH IS SHOWN
 ON THE PLANS TO BE "DONE BY OTHERS."
 5) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE ADDED GAS
 APPLIANCES. WHERE COMBUSTION AIR IS PROVIDED BY THE
 BUILDING?S MECHANICAL VENTILATION SYSTEM, THE SYSTEM
 SHALL PROVIDE THE SPECIFIED COMBUSTION AIR RATE IN
 ADDITION TO THE REQUIRED VENTILATION AIR. 2017 FBC-FUEL
 GAS SEC.304.9.3.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  