| Plan Review Notes For Permit 18080040 |
| Permit Number |
18080040 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2018-10-01 09:19:43 | 1) DETAILS HAVE TO BE SUBMITTED FOR THE INSTALLATION OF | | | THE REINFORCEMENT FOR FUTURE GRAB BARS FOR THE SHOWER | | | AND THE WATER CLOSET.THE DETAILS SHALL COMPLY WITH THE | | | FAIR HOUSING ACT DESIGN MANUAL. THE DETAILS REQUIRED | | | FOR THE REINFORCEMENT SHALL SHOW THE MINIMUM AND | | | MAXIMUM HEIGHTS ABOVE THE FLOOR, THE MINIMUM WIDTH OF | | | THE REINFORCEMENT AND THE MINIMUM LENGTHS. | | | 2) THE GRAB BAR DETAIL NOTE REFERS TO SPECIFICATIONS | | | FOR TYPE OF BARS, ETC. BUT NO SPECIFICATIONS HAVE BEEN | | | SUBMITTED. CLARIFY. | | | | | | TIM LARGE | | | CHIEF PLUMBING INSPECTOR | | | PLUMBING PLAN REVIEW | | | 561-805-6692 | | | [email protected] | | | | | | | | | |
|