| 2018-08-14 14:04:50 | 1) THE RENOVATED TOILET ROOM IN THE MASTER BATH THAT IS |
| | UNDER THE MASTER #18021018 DOES NOT COMPLY WITH THE |
| | FAIR HOUSING ACT. THE BIDET HAS BEEN REMOVED AND THE |
| | NEW SIZE OF THE TOILET ROOM APPEARS TO BE IN VIOLATION. |
| | THE TOILET REQUIRES A CLEAR FLOOR SPACE IN COMPLIANCE |
| | WITH THE FAIR HOUSING ACT DESIGN MANUAL. THIS TOILET |
| | ROOM WAS ORIGINALLY DESIGNED UNDER A SPECIFICATION "B" |
| | TYPE BATHROOM AND MUST MEET ONE OF THE REQUIRED CLEAR |
| | FLOOR SPACES FOR THE WATER CLOSET.A CLEAR FLOOR SPACE |
| | MEASURING A MINIMUM OF 30 INCHES WIDE BY 48 INCHES DEEP |
| | MUST BE PROVIDED OUTSIDE THE SWING OF THE DOOR IN THIS |
| | TOILET ROOM. |
| | 2) BATH #3 DOES NOT COMPLY WITH THE FAIR HOUSING ACT |
| | DESIGN MANUAL.IN ORDER FOR THIS BATHROOM TO COMPLY A |
| | MINIMUM 30 INCH WIDE BY 48 INCH DEEP CLEAR FLOOR SPACE |
| | SHALL BE PROVIDED PARALLEL TO THE SHOWER, AND FLUSH |
| | WITH THE CONTROL WALL. THE TOILET IS NOT PERMITTED TO |
| | ENCROACH INTO THIS CLEAR FLOOR SPACE. AS DESIGNED, THIS |
| | BATHROOM DOES NOT COMPLY WITH THE FAIR HOUSING ACT AND |
| | DOES NOT APPEAR TO BE ABLE TO COMPLY.A CLEAR FLOOR |
| | SPACE MEASURING A MINIMUM OF 30 INCHES WIDE BY 48 |
| | INCHES DEEP MUST BE PROVIDED OUTSIDE THE SWING OF THE |
| | DOOR IN THIS BATHROOM ALSO. |
| | 3) THERE ARE DETAILS LACKING FOR REINFORCEMENT FOR GRAB |
| | BARS, THE DESIGN SPECIFICATION BATHROOM TYPE, MINIMUM |
| | SPACE FOR THE WATER CLOSET, HEIGHT OF THE LAVATORY, |
| | ETC. |
| | NOTE: THE 5 FOOT TURNING DIAMETER SHOWN IN BATHROOM # 3 |
| | HAS NOTHING TO DO WITH FAIR HOUSING AND I DON'T |
| | UNDERSTAND WHY THIS IS BEING SHOWN ON THE PLAN. |
| | CLARIFY. |
| | |
| | TIM LARGE |
| | CHIEF PLUMBING INSPECTOR |
| | PLUMBING PLAN REVIEW |
| | 561-805-6692 |
| | [email protected] |
| | |
| | |