| 2019-03-19 08:39:04 | MECHANICAL PROVISOS | | | | | | 1) SMOKE DETECTORS REQUIRED IN THE HP SUPPLY SYSTEMS | | | AND RETURN AIR CLOSETS. | | | 2) NON-COMBUSTIBLE DOORS REQUIRED FOR ALL AC CLOSETS. | | | 3) DRYER AND KITCHEN COOKING EXHAUST DUCTS SHALL NOT | | | RUN THROUGH PLENUMS. | | | 4) DRYER BOOSTER FAN SHALL BE UL LISTED AND LABELED | | | 5) ACCESS REQUIRED FOR THE DRYER BOOSTER FAN. | | | 6) MANUFACTURER'S SPECIFICATIONS FOR THE ELECTRIC AND | | | GAS-FIRED COOKING APPLIANCES, KITCHEN HOOD AND EXHAUST | | | DUCT, DRYER AND DRYER BOOSTER FAN SHALL BE ONSITE AT | | | TIME OF INSPECTION. | | | 7) ALL ELECTRIC COOKING APPLIANCES SHALL BE UL LISTED | | | AND LABELED FOR RESIDENTIAL USE. | | | 8) KITCHEN EXHAUST HOOD SHALL BE A TYPE II HEAT HOOD | | | LISTED AND LABELED FOR DOMESTIC USE. | | | 9) FIRE DAMPERS NOT ALLOWED IN THE KITCHEN EXHAUST | | | DUCT. | | | |
|