2019-03-19 08:39:04MECHANICAL PROVISOS
  
 1) SMOKE DETECTORS REQUIRED IN THE HP SUPPLY SYSTEMS
 AND RETURN AIR CLOSETS.
 2) NON-COMBUSTIBLE DOORS REQUIRED FOR ALL AC CLOSETS.
 3) DRYER AND KITCHEN COOKING EXHAUST DUCTS SHALL NOT
 RUN THROUGH PLENUMS.
 4) DRYER BOOSTER FAN SHALL BE UL LISTED AND LABELED
 5) ACCESS REQUIRED FOR THE DRYER BOOSTER FAN.
 6) MANUFACTURER'S SPECIFICATIONS FOR THE ELECTRIC AND
 GAS-FIRED COOKING APPLIANCES, KITCHEN HOOD AND EXHAUST
 DUCT, DRYER AND DRYER BOOSTER FAN SHALL BE ONSITE AT
 TIME OF INSPECTION.
 7) ALL ELECTRIC COOKING APPLIANCES SHALL BE UL LISTED
 AND LABELED FOR RESIDENTIAL USE.
 8) KITCHEN EXHAUST HOOD SHALL BE A TYPE II HEAT HOOD
 LISTED AND LABELED FOR DOMESTIC USE.
 9) FIRE DAMPERS NOT ALLOWED IN THE KITCHEN EXHAUST
 DUCT.
  