Plan Review Notes
Plan Review Notes For Permit 18080002
Permit Number 18080002
Review Stop P
Sequence Number 2
Notes
Date Text
2019-01-17 09:16:49 
 2ND REVIEW: 18080002
 2017 FLORIDA BUILDING CODE 6TH EDITION
 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION
 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH
 EDITION
 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH
 EDITION
  
 PLUMBING COMMENTS:
  
 PREVIOUS COMMENT NOT COMPLIED 1. PLEASE PROVIDE DETAILS
 SHOWING THE HEIGHT DIMENSIONS FOR THE GRAB BAR BACKING.
 PER FHA DESIGN MANUAL REQUIREMENT #6 PG. 6.3 - 6.13
  
 NEW COMMENTS:
  
 1. PLEASE SHOW COMPLIANCE GRAB BAR BACKING IS REQUIRED
 IN ALL THE BATHROOMS REGARDLESS IF IT'S SPEC A OR B.
 PER FHA DESIGN MANUAL CH 6 PG. 6.3
  
 2. SHT. P401 ON SOIL STACK S1 FOR BATH 3-4 THE
 HORIZONTAL WET VENT FOR THE TWO SHOWERS SHALL NOT BE
 OFFSET, THE MAIN SECTION OF THE HORIZONTAL WET VENT
 PIPE IS INTENDED TO BE INSTALLED HORIZONTALLY WITHOUT
 ANY OFFSETS WITH EACH DRAIN CONNECTED INDEPENDENTLY TO
 THE HORIZONTAL DRAIN IN ORDER TO KEEP FLOW TURBULENCE
 AT A MINIMUM. FBC PL 912.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  