| | 2ND REVIEW: 18080002 |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | PREVIOUS COMMENT NOT COMPLIED 1. PLEASE PROVIDE DETAILS |
| | SHOWING THE HEIGHT DIMENSIONS FOR THE GRAB BAR BACKING. |
| | PER FHA DESIGN MANUAL REQUIREMENT #6 PG. 6.3 - 6.13 |
| | |
| | NEW COMMENTS: |
| | |
| | 1. PLEASE SHOW COMPLIANCE GRAB BAR BACKING IS REQUIRED |
| | IN ALL THE BATHROOMS REGARDLESS IF IT'S SPEC A OR B. |
| | PER FHA DESIGN MANUAL CH 6 PG. 6.3 |
| | |
| | 2. SHT. P401 ON SOIL STACK S1 FOR BATH 3-4 THE |
| | HORIZONTAL WET VENT FOR THE TWO SHOWERS SHALL NOT BE |
| | OFFSET, THE MAIN SECTION OF THE HORIZONTAL WET VENT |
| | PIPE IS INTENDED TO BE INSTALLED HORIZONTALLY WITHOUT |
| | ANY OFFSETS WITH EACH DRAIN CONNECTED INDEPENDENTLY TO |
| | THE HORIZONTAL DRAIN IN ORDER TO KEEP FLOW TURBULENCE |
| | AT A MINIMUM. FBC PL 912.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |