Plan Review Notes
Plan Review Notes For Permit 18080002
Permit Number 18080002
Review Stop M
Sequence Number 2
Notes
Date Text
2019-01-14 13:36:451ST REVIEW FBC-2010 MECHANICAL
 PERMIT #18080002
 10/3/2018
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE- 2010
 FBC M- FLORIDA MECHANICAL CODE- 2010
 FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010
 FBC FG- FLORIDA FUEL GAS CODE- 2010
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC 2010
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) SHEET M100: THE REQUIRED SMOKE DETECTORS IN BOTH THE
 PLENUM CLOSETS AND SUPPLY DUCTS WERE NOT PROVIDED FOR
 HP- B,C, & E.
  
 2) M100 & M101: PLEASE CHOOSE ONE SMOKE DETECTOR
 IDENTIFICATION SYMBOL OR THE OTHER- S OR SD.
  
 3) M101: THE FIRE DAMPERS IN THE KITCHEN EXHAUST AND
 MAKEUP AIR DUCTS ARE NOT REQUIRED PER SECTION 607.5.5
 (5). PLEASE REMOVE THE DAMPER AND PROVIDE PROTECTION
 FOR THE BOTTOM OF THE SHAFT ENCLOSURE IN COMPLIANCE
 WITH SECTION 607.5.5.1 FBC M, AND 713.1.1 FBC B.
  
 4) M101: AS PREVIOUSLY REQUESTED PLEASE INDICATE THE
 TYPE OF EXHAUST AND MAKEUP AIR DUCTS TO BE INSTALLED
 AND PROVIDE PRODUCT SUBMITTALS FOR THE DUCTS AND THE
 THE KITCHEN EXHAUST HOOD.
  
 5) M101: PLACE A NOTE INDICATING AN ACCESS PANEL WILL
 BE PROVIDED FOR THE DRYER BOOSTER FAN.
  
 6) COMMENTS #7, 8, & 10 FROM THE 1ST REVIEW PRINTED
 BELOW STILL EXIST- PLEASE COMPLY.
  
 7) PROVIDE A CALCULATION TABLE ON THE PLAN SHOWING THE
 TOTAL LENGTH OF THE DRYER EXHAUST DUCT RUN, AND THE
 MAXIMUM ALLOWABLE RUN DISTANCE PER THE MANUFACTURER'S
 SPECIFICATIONS FOR THE DRYER AND THE NEW BOOSTER FAN--
 SECTIONS 504.6.4.1 & 506.4.2 FBC M. (THIS COMMENT IS
 NOW MODIFIED TO INLUDE THE NEW DRYER BOOSTER FAN.
 PLEASE SEE THE EXCEPTION UNDER SECTION 504.6.4.1 FOR
 REQUIRED BOOSTER FAN LABEL).
  
 8) PROVIDE CONSTRUCTION DETAILS FOR THE DRYER EXHAUST
 DUCT ENCLOSURE AND VERIFY THAT THE EQUIVALENT LENGTH OF
 THE EXHAUST DUCT SHALL BE INDENTIFIED ON A PERMANENT
 LABEL OR TAG- SECTION 504.6.5 FBC M. (THE REQUIRED
 DETAIL WAS NOT PROVIDED ON THE ARCHITECTURAL PLANS AS
 WAS STATED IN RESPONSE NARRATIVE. PLEASE PROVIDE THE
 DETAIL.)
  
 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER,
 THE COOKING APPLIANCES, THE WALK-IN COOLER, AND THE
 FIREPLACE.(PRIOR TO PURCHASE AND INSTALLATION, IT IS
 ESSENTIAL TO VERIFY ALL APPLIANCES AND EQUIPMENT ARE
 LISTED AND LABELED IN ACCORDANCE WITH THE FLORIDA
 CODES.)
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  