| 2019-01-14 13:36:45 | 1ST REVIEW FBC-2010 MECHANICAL |
| | PERMIT #18080002 |
| | 10/3/2018 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC B- FLORIDA BUILDING CODE- 2010 |
| | FBC M- FLORIDA MECHANICAL CODE- 2010 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE- 2010 |
| | FBC FG- FLORIDA FUEL GAS CODE- 2010 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC 2010 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) SHEET M100: THE REQUIRED SMOKE DETECTORS IN BOTH THE |
| | PLENUM CLOSETS AND SUPPLY DUCTS WERE NOT PROVIDED FOR |
| | HP- B,C, & E. |
| | |
| | 2) M100 & M101: PLEASE CHOOSE ONE SMOKE DETECTOR |
| | IDENTIFICATION SYMBOL OR THE OTHER- S OR SD. |
| | |
| | 3) M101: THE FIRE DAMPERS IN THE KITCHEN EXHAUST AND |
| | MAKEUP AIR DUCTS ARE NOT REQUIRED PER SECTION 607.5.5 |
| | (5). PLEASE REMOVE THE DAMPER AND PROVIDE PROTECTION |
| | FOR THE BOTTOM OF THE SHAFT ENCLOSURE IN COMPLIANCE |
| | WITH SECTION 607.5.5.1 FBC M, AND 713.1.1 FBC B. |
| | |
| | 4) M101: AS PREVIOUSLY REQUESTED PLEASE INDICATE THE |
| | TYPE OF EXHAUST AND MAKEUP AIR DUCTS TO BE INSTALLED |
| | AND PROVIDE PRODUCT SUBMITTALS FOR THE DUCTS AND THE |
| | THE KITCHEN EXHAUST HOOD. |
| | |
| | 5) M101: PLACE A NOTE INDICATING AN ACCESS PANEL WILL |
| | BE PROVIDED FOR THE DRYER BOOSTER FAN. |
| | |
| | 6) COMMENTS #7, 8, & 10 FROM THE 1ST REVIEW PRINTED |
| | BELOW STILL EXIST- PLEASE COMPLY. |
| | |
| | 7) PROVIDE A CALCULATION TABLE ON THE PLAN SHOWING THE |
| | TOTAL LENGTH OF THE DRYER EXHAUST DUCT RUN, AND THE |
| | MAXIMUM ALLOWABLE RUN DISTANCE PER THE MANUFACTURER'S |
| | SPECIFICATIONS FOR THE DRYER AND THE NEW BOOSTER FAN-- |
| | SECTIONS 504.6.4.1 & 506.4.2 FBC M. (THIS COMMENT IS |
| | NOW MODIFIED TO INLUDE THE NEW DRYER BOOSTER FAN. |
| | PLEASE SEE THE EXCEPTION UNDER SECTION 504.6.4.1 FOR |
| | REQUIRED BOOSTER FAN LABEL). |
| | |
| | 8) PROVIDE CONSTRUCTION DETAILS FOR THE DRYER EXHAUST |
| | DUCT ENCLOSURE AND VERIFY THAT THE EQUIVALENT LENGTH OF |
| | THE EXHAUST DUCT SHALL BE INDENTIFIED ON A PERMANENT |
| | LABEL OR TAG- SECTION 504.6.5 FBC M. (THE REQUIRED |
| | DETAIL WAS NOT PROVIDED ON THE ARCHITECTURAL PLANS AS |
| | WAS STATED IN RESPONSE NARRATIVE. PLEASE PROVIDE THE |
| | DETAIL.) |
| | |
| | 10) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR THE DRYER, |
| | THE COOKING APPLIANCES, THE WALK-IN COOLER, AND THE |
| | FIREPLACE.(PRIOR TO PURCHASE AND INSTALLATION, IT IS |
| | ESSENTIAL TO VERIFY ALL APPLIANCES AND EQUIPMENT ARE |
| | LISTED AND LABELED IN ACCORDANCE WITH THE FLORIDA |
| | CODES.) |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS. |
| | |