| 2018-10-10 13:40:43 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | PLUMBING COMMENTS: |
| | |
| | 1. PLEASE PROVIDE DETAILS SHOWING THE HEIGHT DIMENSIONS |
| | FOR THE GRAB BAR BACKING. PER FHA DESIGN MANUAL |
| | REQUIREMENT #6 PG. 6.3 - 6.13 |
| | |
| | 2. SHOW CLEAR FLOOR SPACE FOR THE TOILET YOU SHOW A |
| | 30'X48" IT SHALL BE 48X56 THE ROOM IT IS IN SHOWS A |
| | DIMENSION OF 47 1/4" PLEASE CLARIFY. PER FHA DESIGN |
| | MANUAL REQUIREMENT #7 PG. 7.43 |
| | |
| | 3. THE CLEAR FLOOR SPACE FOR THE SHOWER AND THE |
| | LAVATORY SHALL BE SHOWN FLUSH AGAINST THE FIXTURE WITH |
| | THE SPACE FOR THE LAVATORY CENTERED ON THE LAVATORY AND |
| | THE ONE FOR THE SHOWER THE END EVEN WITH THE CONTROL |
| | WALL . PER FHA DESIGN MANUAL REQUIREMENT #7 PG 7.47 |
| | +7.53 + 7.56 |
| | |
| | 4. PLEASE PROVIDE ISOMETRIC DRAWINGS FOR THE SANITARY, |
| | WATER AND GAS. PER WPB AMEND TO FBC 107.3.5.1.3(13) + |
| | 107.3.5.1.5(9) |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |