Plan Review Notes
Plan Review Notes For Permit 18080002
Permit Number 18080002
Review Stop B
Sequence Number 1
Notes
Date Text
2018-10-22 16:24:35****CORRECTIONS****
 W.P.B. PERMIT: 18080002
 REVIEWED: OCTOBER 22, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER I
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC ENERGY = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 1. PLEASE CHANGE GOVERNING CODES FOR THIS UNIT TO BE
 FBC 2010. THIS IS DUE TO THE FACT THAT THE BUILDING HAS
 NO C.O. THE BUILDING OFFICIAL HAS REQUESTED ALL WORK TO
 BE DONE UNDER 2010 CODE ADDITION AT THIS TIME.
  
 2. [FBC AMENDED 107.3.5]PROVIDE DATA FOR EXISTING FLOOR
 LIVE/DEAD LOADING DESIGN AND PROPOSED LIVE/DEAD LOADS.
  
 3. [FBC AMENDED 107.3.5]PROVIDE AREA TABULATIONS FOR
 LIVING SPACE UNDER AIR AND OUTDOOR SPACE.
  
 4. PROVIDE SUBMITTAL FOR FLOORING WITH UNDERLAYMENT TO
 BE USED FOR EACH TYPE OF FLOORING, OR INDICATE THAT THE
 SUBMITTAL WILL BE DEFERRED.
 INCLUDE LOCATION, AREA, FLOORING TYPE, CEILING ASSEMBLY
 BELOW AND FLOOR THICKNESS. TWO COMPLETE COLLATED SETS
 OF ALL DOCUMENTS REQUIRED.
  
 PLEASE NOTE THAT TEST REPORTS ARE REQUIRED -
 MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO
 DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST
 REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE
 MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT)
  
 A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM
 CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED
 GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT.
  
 C. FBC 603.1, ALLOWABLE MATERIALS IN NON-COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE
 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84
 OR UL 723.
  
 5. [FBC 107.3.5]PROVIDE INTERIOR ELEVATIONS FOR KITCHEN
 AND TYPICAL BATHROOM.
  
 6. ARE PLUMBING PIPES IN THE SLAB ALREADY OR WILL THE
 FLOORS BE CUT?
  
 7. SEPARATE PERMIT REQ'D FOR SMOKE ALARM.
  
 NOTE:
 -THE CONTRACTOR WILL BE RESPONSIBLE TO MAINTAIN THE
 INTEGRITY OF THE EXISTING POST TENSION FLOORS. ANY
 MODIFICATIONS THAT INVOLVE CHANGES IN THE POST TENSION
 FLOORS WILL REQUIRE A SPECIAL INSPECTOR AT THE EXPENSE
 OF THE PERMIT HOLDER.
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  