| 2018-10-22 16:24:35 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18080002 |
| | REVIEWED: OCTOBER 22, 2018 |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER I |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC AMENDED = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC ENERGY = FBC ENERGY CONSERVATION |
| | FBC R = FBC RESIDENTIAL |
| | |
| | 1. PLEASE CHANGE GOVERNING CODES FOR THIS UNIT TO BE |
| | FBC 2010. THIS IS DUE TO THE FACT THAT THE BUILDING HAS |
| | NO C.O. THE BUILDING OFFICIAL HAS REQUESTED ALL WORK TO |
| | BE DONE UNDER 2010 CODE ADDITION AT THIS TIME. |
| | |
| | 2. [FBC AMENDED 107.3.5]PROVIDE DATA FOR EXISTING FLOOR |
| | LIVE/DEAD LOADING DESIGN AND PROPOSED LIVE/DEAD LOADS. |
| | |
| | 3. [FBC AMENDED 107.3.5]PROVIDE AREA TABULATIONS FOR |
| | LIVING SPACE UNDER AIR AND OUTDOOR SPACE. |
| | |
| | 4. PROVIDE SUBMITTAL FOR FLOORING WITH UNDERLAYMENT TO |
| | BE USED FOR EACH TYPE OF FLOORING, OR INDICATE THAT THE |
| | SUBMITTAL WILL BE DEFERRED. |
| | INCLUDE LOCATION, AREA, FLOORING TYPE, CEILING ASSEMBLY |
| | BELOW AND FLOOR THICKNESS. TWO COMPLETE COLLATED SETS |
| | OF ALL DOCUMENTS REQUIRED. |
| | |
| | PLEASE NOTE THAT TEST REPORTS ARE REQUIRED - |
| | MANUFACTURER SPEC SHEETS ARE NOT ACCEPTABLE DUE TO |
| | DISCREPANCIES BETWEEN SPEC SHEETS/BROCHURES AND TEST |
| | REPORTS FOR SOME MANUFACTURERS (NOT NECESSARILY THE |
| | MANUFACTURER SELECTED; THIS IS A GENERAL COMMENT) |
| | |
| | A. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING |
| | DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR |
| | SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS |
| | (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR |
| | BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90. |
| | THE TEST REPORT CANNOT INCLUDE A DROPPED GYPSUM |
| | CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | B. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN |
| | DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC |
| | OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN |
| | IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN |
| | 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH |
| | ASTM E 492. THE TEST REPORT CANNOT INCLUDE A DROPPED |
| | GYPSUM CEILING. PROVIDE A COPY OF THE TEST REPORT. |
| | |
| | C. FBC 603.1, ALLOWABLE MATERIALS IN NON-COMBUSTIBLE |
| | BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL |
| | INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| | DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| | TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. SEE |
| | 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM E 84 |
| | OR UL 723. |
| | |
| | 5. [FBC 107.3.5]PROVIDE INTERIOR ELEVATIONS FOR KITCHEN |
| | AND TYPICAL BATHROOM. |
| | |
| | 6. ARE PLUMBING PIPES IN THE SLAB ALREADY OR WILL THE |
| | FLOORS BE CUT? |
| | |
| | 7. SEPARATE PERMIT REQ'D FOR SMOKE ALARM. |
| | |
| | NOTE: |
| | -THE CONTRACTOR WILL BE RESPONSIBLE TO MAINTAIN THE |
| | INTEGRITY OF THE EXISTING POST TENSION FLOORS. ANY |
| | MODIFICATIONS THAT INVOLVE CHANGES IN THE POST TENSION |
| | FLOORS WILL REQUIRE A SPECIAL INSPECTOR AT THE EXPENSE |
| | OF THE PERMIT HOLDER. |
| | -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| | EACH COMMENT IS BEING ADDRESSED. |
| | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| | OF MATERIALS REQUESTED. |
| | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| | OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| | APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| | NEED "VOID", RENDERING THEM NOT USABLE. |
| | |