| 2018-09-04 09:21:43 | ****CORRECTIONS**** |
| | W.P.B. PERMIT: 18071460 |
| | REVIEWED: SEPTEMBER 04, 2018 |
| | 2ND REVIEW |
| | |
| | DYLAN BATTLES |
| | BUILDING PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| | FBC B = FBC BUILDING |
| | FBC EB = FBC EXISTING BUILDING |
| | FBC A = FBC ACCESSIBILITY |
| | FBC EC = FBC ENERGY CONSERVATION |
| | |
| | 1-8 OK. |
| | |
| | NEW COMMENTS: |
| | THE LOAD CALCULATION I WAS ASKING ABOUT IN 1ST REVIEW |
| | ITEM #6 WAS FOR THE WEIGHT OF THE GENERATOR TO BE |
| | SUPPORTED. NOW THE GENERATOR HAS SHIFTED ORIENTATION |
| | AND IS ON A STAND. |
| | |
| | 9. [FBC 1510.10]PLEASE PROVIDE THE SIZE OF THE UNIT AND |
| | FOLLOW CLEARANCE REQUIREMENTS FROM TABLE 1510.10. |
| | ADJUST ORIENTATION OF FUTURE UNIT ON SHEET A-105R TO |
| | MATCH STRUCTURAL SHEETS. |
| | |
| | 10. [FBC 1511.1.1]WHAT PERCENTAGE OF ROOF IS BEING |
| | REPLACED? IF IT EXCEEDS 25% THAN THE WHOLE ROOF SHOULD |
| | BE REPLACED TO MEET CURRENT CODES. |
| | |
| | AS DISCUSSED WITH THE CONTRACTOR THIS PERMIT WAS TO |
| | ALLOW SOME STRUCTURAL WORK TO START WHILE THE MAIN |
| | PERMIT WAS BEING COMPLETED. |
| | THE PLANS STILL SHOW WORK BEYOUND WHAT WAS DISCUSSED. |
| | PLEASE REMOVE ELEMENTS FROM PLANS THAT ADD SPACE OR |
| | THAT WOULD REQUIRE LIFE SAFETY REVIEWS. |
| | |
| | NOTE: |
| | ALL WORK BEING PERFORMED IN PERMIT 18071460 IS BEING |
| | DONE WITHOUT REVIEWS FROM MULTI-DISIPLINES. ANY |
| | DEVIATIONS THAT MAY OCCUR FROM THE REVIEWS OF BUILD OUT |
| | PERMIT WOULD BE AT THE RISK OF THE OWNER AND |
| | CONTRACTOR. |
| | |