Plan Review Notes
Plan Review Notes For Permit 18071460
Permit Number 18071460
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-16 10:51:43****CORRECTIONS****
 W.P.B. PERMIT: 18071460
 REVIEWED: AUGUST 13, 2018
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6718
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. PROJECT EVALUATION SEEMS LOW FOR THE SCOPE SHOWN ON
 PLANS. THE ROOFING WOULD BE INCLUDED IN THE PROJECT
 VALUE AND WOULD BE ISSUED AS ZERO DOLLAR SUB-PERMIT.
 PLEASE PROVIDE COST ESTIMATE, OR CONTRACT TO SHOW
 VALUES OF ALL WORK THAT WILL BE PART OF THIS PERMIT
 (GENERATOR TO BE SEPARATE PERMIT WITH SEPARATE COST
 ASSOCIATED WITH IT)
  
 2. PROVIDE DETAILED DESCRIPTION OF THIS PERMIT?
 IS THERE A PERMIT COMING FOR TENANT BUILD-OUT?
 THE DRAWINGS SHOW THINGS THAT WOULD NEED MORE DESIGN.
 PLEASE ADJUST DRAWINGS TO MATCH THE SCOPE OF WORK
 INTENDED AND I CAN REVIEW.
  
 3. IT SEEMS THAT YOU ARE LOOKING TO START WORK ON
 GENERATOR. I HAVE THE FOLLOWING COMMENTS FOR JUST THAT
 PORTION, BUT I NEED MORE DETAILED PLANS FOR THE ENTRY
 WAY WORK AND THE ENCLOSING OF SEPERARTION BETWEEN THE
 BUILDINGS.
  
 4. [FBC 107.2.1.1]SUB PERMIT REQ?D FOR ROOFING.
 IS ROOFING PART OF THIS PERMIT?
  
 5. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVALS FOR
 ROOFING, OR INDICATE THAT YOU WOULD LIKE THEM DEFFERED.
  
 6. [FBC 107.2.1.1]PROVIDE ENGINEERING FOR ROOF LOADS
 INCLUDING THE FUTURE GENERATOR.
  
 7. HOW ARE 2X12?S CONNECTED AT WALLS?
  
 8. PROVIDE ROOF SHEATHING ATTACHMENT/SPACING.
  
 9. [FBC 107.2.1.1]HOW IS THE ROOF ACCESSED?
  
 NOTE:
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  