Plan Review Notes
Plan Review Notes For Permit 18071403
Permit Number 18071403
Review Stop P
Sequence Number 2
Notes
Date Text
2018-09-27 07:10:05FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
 PLUMBING COMMENTS: DENIED
  
 1. PROVIDE PIPING MATERIALS TYPE & FIRE RATED
 ASSEMBLIES FOR RELOCATED DRAIN FLOOR PENETRATION, FBC
 107.2.1.
  
 2. ACESSIBLE TEMP LIMITING DEVICE REQUIRED FOR TUB FILL
 VALVE, FBC P 424.3.
  
 3. HI LIMIT THERMOSTATIC / PB CONTROL RQUIRED FOR
 SHOWER VALVE, FBC P 424.5.
  
 4. SHOWER PAN REQUIRED, FBC P 417.8.2.
  
 PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN
 RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES
 INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY
 REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED
 SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID".
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL: [email protected]
 561-805-6715
  