| 2018-10-16 14:13:15 | CODES IN EFFECT: |
| | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| | 6TH ED, CHAPTER 1. |
| | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| | 6TH EDITION |
| | FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| | FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| | FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| | EDITION |
| | FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| | FAC= FLORIDA ADMINISTRATIVE CODE |
| | FS = FLORIDA STATUTES |
| | |
| | 2ND REVIEW: |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. RE: PLAN SHEET P-1; PLAN SHOWS CONNECTION OF NEW 3" |
| | KITCHEN GREASY WASTE TO AN EXISTING 4" GREASY WASTE |
| | BUILDING DRAIN WHICH IS CONNECTED TO AN EXISTING 2000 |
| | GALLON GREASE INTERCEPTOR. WHERE IS 4" GREASY WASTE |
| | COMING FROM? PROVIDE SIZING CALCULATIONS FOR EXISTING |
| | FACILITY AS WELL AS SIZING CALCULATIONS FOR NEW WORK TO |
| | DETERMINE THAT THE INTERCEPTOR IS SIZED TO ACCOMMODATE |
| | ALL PER WPB FBC 107.2.1. |
| | 2. RE: PLAN SHEET P-2; SANITARY ISOMETRIC SHOWS A |
| | COMMON INDIRECT WASTE FROM TWO (2) ITEM #20 HOT FOOD |
| | WELLS TO THE FLOOR SINK. PROVIDE INDEPENDENT INDIRECT |
| | WASTE FOR EACH WELL IN ACCORDANCE WITH 802.1.1 . |
| | |
| | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| | INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| | REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| | SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED "VOID". |
| | |
| | |