| 2018-10-11 09:24:09 | 2ND REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18071384 |
| | 10/12/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) COMMENTS #3- 7 FROM THE 1ST REVIEW PRINTED BELOW |
| | HAVE NOT BEEN COMPLETETY ADDRESSED AND STILL EXIST. |
| | |
| | 3) VERIFY COMPLIANCE WITH SECTION 508.1.1 FBC M- SEE |
| | BELOW. |
| | |
| | 508.1.1 MAKEUP AIR TEMPERATURE. |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 |
| | DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING |
| | AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE |
| | CAPACITY OF THE HVAC SYSTEM. |
| | |
| | (IN RESPONSE TO COMMENT #3 THE ENGINEER STATES IN HIS |
| | RESPONSE THAT THE MAKEUP AIR IS LOCATED IN THE HOOD, |
| | HOWEVER THIS IN NOT THE CASE AS THE MAKEUP AIR IS |
| | DELIVERED VIA AN AIR CURTAIN AT THE FRONT FACE OF THE |
| | HOOD. PLEASE CONSULT WITH CAPTIVEAIRE FOR THE |
| | PERCENTAGE OF AIR THAT IS DIFFUSED INTO THE SPACE AND |
| | HOW THAT HOT AIR IS BEING COOLED TO WITHIN 10 DEGREES |
| | OF THE TEMPERATURE IN THE KITCHEN). |
| | |
| | 4) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEM- SECTION C403.2.1 FBC EC. PLEASE NOTE THAT IF |
| | THE SYSTEM WILL BE USED TO SHOW COMPLIANCE WITH COMMENT |
| | #3 ABOVE, THEN THE CALCS SHOULD SPECIFICALLY ADDRESS |
| | THE HEAT LOAD IN BTUH GAINED FROM THE PERCENTAGE OF |
| | UNCONDITIONED MAKE UP AIR THAT IS NOT EXHAUSTED BY THE |
| | HOOD. |
| | |
| | ( NO AC CALCULATIONS WERE SUBMITTED. PLEASE NOTE THAT |
| | THE CALCULATIONS SHALL INDICATE THE HEAT LOADS FOR |
| | COOKING APPLIANCES, AND ANY OF THE LOAD FROM THE MAKEUP |
| | AIR FOR THE HOOD THAT MAY BE IMPACTING THE KITCHEN |
| | SPACE). |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL |
| | GAS-FIRED COOKING APPLIANCES- SECTION 623.1 FBC FG. |
| | |
| | (NOT SUBMITTED). |
| | |
| | 6) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | GAS-FIRED COOKING APPLIANCES AND INDICATE HOW THE AIR |
| | IS BEING PROVIDED- SECTION 304.1 FBC FG. |
| | |
| | (NOT PROVIDED). |
| | |
| | 7) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| | THE EXTERIOR CONDENSER- SECTION 301.15 FBC M. |
| | |
| | (NOT PROVIDED). |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |