Plan Review Notes
Plan Review Notes For Permit 18071384
Permit Number 18071384
Review Stop M
Sequence Number 2
Notes
Date Text
2018-10-11 09:24:092ND REVIEW FBC-2017 MECHANICAL
 PERMIT #18071384
 10/12/18
  
 CODES IN EFFECT:
  
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) COMMENTS #3- 7 FROM THE 1ST REVIEW PRINTED BELOW
 HAVE NOT BEEN COMPLETETY ADDRESSED AND STILL EXIST.
  
 3) VERIFY COMPLIANCE WITH SECTION 508.1.1 FBC M- SEE
 BELOW.
  
 508.1.1 MAKEUP AIR TEMPERATURE.
 THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE
 AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10
 DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING
 AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE
 CAPACITY OF THE HVAC SYSTEM.
  
 (IN RESPONSE TO COMMENT #3 THE ENGINEER STATES IN HIS
 RESPONSE THAT THE MAKEUP AIR IS LOCATED IN THE HOOD,
 HOWEVER THIS IN NOT THE CASE AS THE MAKEUP AIR IS
 DELIVERED VIA AN AIR CURTAIN AT THE FRONT FACE OF THE
 HOOD. PLEASE CONSULT WITH CAPTIVEAIRE FOR THE
 PERCENTAGE OF AIR THAT IS DIFFUSED INTO THE SPACE AND
 HOW THAT HOT AIR IS BEING COOLED TO WITHIN 10 DEGREES
 OF THE TEMPERATURE IN THE KITCHEN).
  
 4) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW
 AC SYSTEM- SECTION C403.2.1 FBC EC. PLEASE NOTE THAT IF
 THE SYSTEM WILL BE USED TO SHOW COMPLIANCE WITH COMMENT
 #3 ABOVE, THEN THE CALCS SHOULD SPECIFICALLY ADDRESS
 THE HEAT LOAD IN BTUH GAINED FROM THE PERCENTAGE OF
 UNCONDITIONED MAKE UP AIR THAT IS NOT EXHAUSTED BY THE
 HOOD.
  
 ( NO AC CALCULATIONS WERE SUBMITTED. PLEASE NOTE THAT
 THE CALCULATIONS SHALL INDICATE THE HEAT LOADS FOR
 COOKING APPLIANCES, AND ANY OF THE LOAD FROM THE MAKEUP
 AIR FOR THE HOOD THAT MAY BE IMPACTING THE KITCHEN
 SPACE).
  
 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL
 GAS-FIRED COOKING APPLIANCES- SECTION 623.1 FBC FG.
  
 (NOT SUBMITTED).
  
 6) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE
 GAS-FIRED COOKING APPLIANCES AND INDICATE HOW THE AIR
 IS BEING PROVIDED- SECTION 304.1 FBC FG.
  
 (NOT PROVIDED).
  
 7) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE EXTERIOR CONDENSER- SECTION 301.15 FBC M.
  
 (NOT PROVIDED).
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER