| 2018-08-23 11:04:43 | 1ST REVIEW FBC-2017 MECHANICAL |
| | PERMIT #18071384 |
| | 8/23/18 |
| | |
| | CODES IN EFFECT: |
| | |
| | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| | 2017 |
| | FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| | 2017 |
| | FS- FLORIDA STATUTES |
| | FAC- FLORIDA ADMINISTRATIVE CODE |
| | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| | EDITION 2017 |
| | |
| | PLAN REVIEW RESULTS: DENIED. |
| | |
| | 1) ADVISORY: THE CITY OF WEST PALM BEACH BUILDING |
| | DEPARTMENT REQUIRES SEPARATE PERMITS FOR KITCHEN |
| | EXHAUST HOODS AND FIRE SUPPRESSION SYSTEMS- SEE SECTION |
| | 107.2.1 WPB AMENDMENTS TO THE FBC HOWEVER COMMENTS #2 & |
| | 3 BELOW PERTAINING TO THE HOOD SHOULD BE ADDRESSED NOW |
| | TO AVOID CONFLICTS LATER WITH THE HOOD PERMIT. |
| | |
| | 2) THE LOCATION OF THE KEF EXHAUST FAN DOES NOT APPEAR |
| | TO BE IN COMPLIANCE WITH SECTIONS 506.3.13.2 AND |
| | 506.3.13.3 FBC M. PLEASE REVIEW THE CODE SECTIONS BELOW |
| | AND VERIFY COMPLIANCE OR RELOCATE THE TERMINATION. |
| | |
| | 506.3.13.2 TERMINATION THROUGH AN EXTERIOR WALL. |
| | EXHAUST OUTLETS SHALL BE PERMITTED TO TERMINATE THROUGH |
| | EXTERIOR WALLS WHERE THE SMOKE, GREASE, GASES, VAPORS |
| | AND ODORS IN THE DISCHARGE FROM SUCH TERMINATIONS DO |
| | NOT CREATE A PUBLIC NUISANCE OR A FIRE HAZARD. SUCH |
| | TERMINATIONS SHALL NOT BE LOCATED WHERE PROTECTED |
| | OPENINGS ARE REQUIRED BY THE FLORIDA BUILDING CODE, |
| | BUILDING. OTHER EXTERIOR OPENINGS SHALL NOT BE LOCATED |
| | WITHIN 3 FEET (914 MM) OF SUCH TERMINATIONS. |
| | |
| | 506.3.13.3 TERMINATION LOCATION. |
| | EXHAUST OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET |
| | (3048 MM) HORIZONTALLY FROM PARTS OF THE SAME OR |
| | CONTIGUOUS BUILDINGS, ADJACENT BUILDINGS AND ADJACENT |
| | PROPERTY LINES AND SHALL BE LOCATED NOT LESS THAN 10 |
| | FEET (3048 MM) ABOVE THE ADJOINING GRADE LEVEL. EXHAUST |
| | OUTLETS SHALL BE LOCATED NOT LESS THAN 10 FEET (3048 |
| | MM) HORIZONTALLY FROM OR NOT LESS THAN 3 FEET (914 MM) |
| | ABOVE AIR INTAKE OPENINGS INTO ANY BUILDING. |
| | |
| | 3) VERIFY COMPLIANCE WITH SECTION 508.1.1 FBC M- SEE |
| | BELOW. |
| | |
| | 508.1.1 MAKEUP AIR TEMPERATURE. |
| | THE TEMPERATURE DIFFERENTIAL BETWEEN MAKEUP AIR AND THE |
| | AIR IN THE CONDITIONED SPACE SHALL NOT EXCEED 10 |
| | DEGREES F (6 DEGREES C) EXCEPT WHERE THE ADDED HEATING |
| | AND COOLING LOADS OF THE MAKEUP AIR DO NOT EXCEED THE |
| | CAPACITY OF THE HVAC SYSTEM. |
| | |
| | 4) PROVIDE COOLING AND HEATING CALCULATIONS FOR THE NEW |
| | AC SYSTEM- SECTION C403.2.1 FBC EC. PLEASE NOTE THAT IF |
| | THE SYSTEM WILL BE USED TO SHOW COMPLIQNCE WITH COMMENT |
| | #3 ABOVE, THEN THE CALCS SHOULD SPECIFICALLY ADDRESS |
| | THE HEAT LOAD IN BTUH GAINED FROM THE PERCENTAGE OF |
| | UNCONDITIONED MAKE UP AIR THAT IS NOT EXHAUSTED BY THE |
| | HOOD. |
| | |
| | 5) SUBMIT MANUFACTURER'S SPECIFICATIONS FOR ALL |
| | GAS-FIRED COOKING APPLIANCES- SECTION 623.1 FBC FG. |
| | |
| | 6) PROVIDE COMBUSTION AIR CALCULATIONS FOR THE |
| | GAS-FIRED COOKING APPLIANCES AND INDICATE HOW THE AIR |
| | IS BEING PROVIDED- SECTION 304.1 FBC FG. |
| | |
| | 7) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF |
| | THE EXTERIOR CONDENSER- SECTION 301.15 FBC M. |
| | |
| | |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| | KEEP THEM WITH THE SUBMITTALS |
| | |