| 2018-08-28 18:02:57 | 1ST REVIEW: |
| | 2017 FLORIDA BUILDING CODE 6TH EDITION |
| | 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| | 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| | EDITION |
| | 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| | EDITION |
| | |
| | GAS COMMENTS: |
| | 1. OUR RECORDS SHOW THAT THERE IS EXITING LP GAS TANK |
| | PROVIDING GAS FOR THE KITCHEN WITH A TOTAL BTU LOAD OF |
| | 500,000 UNDER PERMIT #05090527 IT LIST NATURAL GAS ON |
| | THE NEW PLANS PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 2. PLEASE SHOW THE EXISTING BTU LOAD ON THE PLAN THE |
| | PIPING FROM THE LP TANK TO THE BRANCH FOR THE NEW LOAD |
| | BE NEED TO BE RESIZED. PER FBC FG 402.4 |
| | 3. SHOW EXITING PIPING ON RISER WITH SIZE BACK TO THE |
| | LP TANK. PER WPB AMEND TO FBC 107.2.1 |
| | 4. THE TOTAL BTU LOAD SHOWN ON THE RISER ADDS UP TO |
| | 493,000 BTU THE TOTAL LOAD LISTED ON SIZING TABLE NOTES |
| | IS 547,000 BTU PLEASE CLARIFY. PER WPB AMEND TO FBC |
| | 107.2.1 |
| | 5. SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC-FUEL GAS CODE SEC.304.1, 614.6 (CLOTHES DRYERS) OR |
| | 2017 FBC-RES. SEC. G 2407.1 AND G2439.4 (. |
| | 6. SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT AND |
| | REGULATORS TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| | NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND |
| | 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES |
| | SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS |
| | FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT |
| | THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES. |
| | SEC.G2408.1. |
| | 7. THE DISTANCE ON YOUR .5LB SYSTEM IS LISTED AS 106? |
| | PER FBC FG (1) THE PIPING SHALL BE 2? PLEASE CLARIFY. |
| | PER WPB AMEND TO FBC 107.2.1 |
| | |
| | PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| | RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| | CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| | THE PREVIOUSLY REVIEWED SHEETS. |
| | |
| | GEORGE JOHNSON |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561-805-6711 |
| | [email protected] |
| | |