| Plan Review Notes For Permit 18071384 |
| Permit Number |
18071384 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-29 15:04:15 | PLAN | | | REVIEW COMMENTS | | | | | | 1ST REVIEW: FBC SIXTH EDITION (2017) | | | ROBERT MCDOUGAL, CBO | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561) 805-6714 | | | [email protected] | | | | | | DENIED BY BUILDING | | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | | | 1) SHEET ID-1.3 OF THE PLANS REFERENCES TO THE 2014 FBC | | | UNDER GENERAL NOTES. UNDER THE BUILDING CODE IN EFFECT | | | SECTION THE FIFTH EDITION IS SPECIFIED FOR THE 2017 FBC | | | AND IT SHOULD BE THE SIXTH EDITION. THE FBC SIXTH | | | EDITION (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL | | | NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE | | | REQUIRED TO COMPLY WITH AND REFERENCE THE FBC SIXTH | | | EDITION (2017). | | | FS CHAPTER 553 | | | | | | 2) SPECIFY THE FOLLOWING DESIGN CRITERIA: 1) TYPE OF | | | CONSTRUCTION, 2) OCCUPANCY TYPE 3) FIRE SPRINKLERED, 4) | | | WIND SPEED AND 5) EXPOSURE CATEGORY FBC 107.2.1 | | | | | | 3) IT DOES NOT APPEAR THAT THE KITCHEN AREA WOULD BE | | | REQUIRED TO HAVE ONE HOUR FIRE RATED WALLS AND | | | CEILINGS. PLEASE EXPLAIN. FBC 107.2.1 | | | | | | 4) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A | | | RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE | | | CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | | KEEP THEM WITH THE SUBMITTALS. |
|