Plan Review Notes
Plan Review Notes For Permit 18071384
Permit Number 18071384
Review Stop B
Sequence Number 1
Notes
Date Text
2018-08-29 15:04:15PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) SHEET ID-1.3 OF THE PLANS REFERENCES TO THE 2014 FBC
 UNDER GENERAL NOTES. UNDER THE BUILDING CODE IN EFFECT
 SECTION THE FIFTH EDITION IS SPECIFIED FOR THE 2017 FBC
 AND IT SHOULD BE THE SIXTH EDITION. THE FBC SIXTH
 EDITION (2017) WENT INTO EFFECT ON JANUARY 1, 2018. ALL
 NEW PERMITS APPLIED FOR ON OR AFTER THAT DATE ARE
 REQUIRED TO COMPLY WITH AND REFERENCE THE FBC SIXTH
 EDITION (2017).
 FS CHAPTER 553
  
 2) SPECIFY THE FOLLOWING DESIGN CRITERIA: 1) TYPE OF
 CONSTRUCTION, 2) OCCUPANCY TYPE 3) FIRE SPRINKLERED, 4)
 WIND SPEED AND 5) EXPOSURE CATEGORY FBC 107.2.1
  
 3) IT DOES NOT APPEAR THAT THE KITCHEN AREA WOULD BE
 REQUIRED TO HAVE ONE HOUR FIRE RATED WALLS AND
 CEILINGS. PLEASE EXPLAIN. FBC 107.2.1
  
 4) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.