| Plan Review Notes For Permit 18071367 |
| Permit Number |
18071367 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-06 11:11:49 | W.P.B. PERMIT: 18071367 | | | | | | 1. PLEASE PROVIDE COPY OF HOA APPROVAL LETTER FOR THE | | | VINYL REPLACEMENT WINDOWS. | | | | | | 2. WHAT IS THE SHGC OF NEW GLASS? | | | [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN EXISTING | | | FENESTRATION UNIT IS REPLACED WITH A NEW FENESTRATION | | | PRODUCT, INCLUDING SASH AND GLAZING, THE REPLACEMENT | | | FENESTRATION UNIT SHALL MEET THE APPLICABLE | | | REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE | | | R402.1.2. | | | NEW FENESTRATION SHOULD HAVE MAXIMUM SOLAR HEAT GAIN | | | CO-EFFICIENT (SHGC) OF 0.25 IN CLIMATE ZONE 1. | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|