Plan Review Notes
Plan Review Notes For Permit 18071331
Permit Number 18071331
Review Stop P
Sequence Number 2
Notes
Date Text
2019-04-29 13:45:27PLUMBING 2ND REVIEW**DENIED**
  
 1) ONLY 1 NEW SHT S1 WAS PROVIDE. 2 COPIES OF ALL PLANS
 ARE REQUIRED. FBC 107.1
  
 2) PLUMBING ISOMETRIC PLAN DOES NOT MATCH FLOOR PLAN
 LAY OUT OR 2ND ISOMETRIC DRAWING PROVIDED. PLEASE
 CLARIFY AND REMOVE ALL PAGES NOT PART OF THE REVIEW
 PROCESS. FBC 107.3.5
  
 3) SHT. S2 SHOWS GAS TANKLESS SHOWS INSIDE BUT SEPERATE
 SHEET FLAT DRAWING IS SHOWING IT OUTSIDE. PLEASE
 CLARIFY. FBC 107.2.1. PROVIDE DISTANCE FROM ALL DOORS
 AND WINDOWS.
  
  
 TIM HUNT
 PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR
 CITY OF WEST PALM BEACH
 561-248-2703
 [email protected]
 [email protected]
  
  