| 2019-04-29 13:28:15 | GAS 2ND REVIEW**DENIED**THESE ARE THE SAME COMMENTS |
| | FROM PERMIT#19010365. PLEASE NOTE FL ST 553.80 (B)2B |
| | WITH RESPECT TO EVALUATION OF DESIGN PROFESSIONALS? |
| | DOCUMENTS, IF A LOCAL GOVERNMENT FINDS IT NECESSARY, IN |
| | ORDER TO ENFORCE COMPLIANCE WITH THE FLORIDA BUILDING |
| | CODE AND ISSUE A PERMIT, TO REJECT DESIGN DOCUMENTS |
| | REQUIRED BY THE CODE THREE OR MORE TIMES FOR FAILURE TO |
| | CORRECT A CODE VIOLATION SPECIFICALLY AND CONTINUOUSLY |
| | NOTED IN EACH REJECTION, INCLUDING, BUT NOT LIMITED TO, |
| | EGRESS, FIRE PROTECTION, STRUCTURAL STABILITY, ENERGY, |
| | ACCESSIBILITY, LIGHTING, VENTILATION, ELECTRICAL, |
| | MECHANICAL, PLUMBING, AND GAS SYSTEMS, OR OTHER |
| | REQUIREMENTS IDENTIFIED BY RULE OF THE FLORIDA BUILDING |
| | COMMISSION ADOPTED PURSUANT TO CHAPTER 120, THE LOCAL |
| | GOVERNMENT SHALL IMPOSE, EACH TIME AFTER THE THIRD SUCH |
| | REVIEW THE PLANS ARE REJECTED FOR THAT CODE VIOLATION, |
| | A FEE OF FOUR TIMES THE AMOUNT OF THE PROPORTION OF THE |
| | PERMIT FEE ATTRIBUTED TO PLANS REVIEW. |
| | IT IS RECOMMENDED FOR YOU TO COME IN AND MEET WITH THE |
| | PLAN REVIEW STAFF BEFORE RESUBMITTING. |
| | |
| | NOTE:THE PLANS INDICATE AN EXISTING GAS METER. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | FGC SECS. 401.4, 401.8, 402.1, 402.2, 402.3 OR FBCR |
| | SECS.G2412.4, G2412.8, G2413.1, G2413.2, G2413.3. |
| | |
| | |
| | 1) SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY SHOWS THE |
| | LENGTH OF ALL CUT SECTIONS OF PIPE. GAS RANGE IS NOT |
| | SHOWING ON GAS ISOMETRIC DRAWING BUT SHOWS AS BEING |
| | RELOCATED. FBC-RES SEC. G2413.4.1, G2413.4.2. |
| | |
| | 2) SUBMIT COMBUSTION AIR CALCULATIONS FOR THE RANGE. |
| | WHERE COMBUSTION AIR IS PROVIDED BY THE BUILDING?S |
| | MECHANICAL VENTILATION SYSTEM, THE SYSTEM SHALL PROVIDE |
| | THE SPECIFIED COMBUSTION AIR RATE IN ADDITION TO THE |
| | REQUIRED VENTILATION AIR. 2017 FBCR G2407.9.3. |
| | |
| | 3) SUBMIT MANUFACTURER?S SPECIFICATION SHEETS / |
| | INSTALLATION MANUAL FOR ALL GAS EQUIPMENT TO VERIFY |
| | COMPLIANCE WITH STANDARDS NFPA 54, NFPA 58, AND |
| | FBC-2017 FUEL GAS CODE SEC. 402.2, AND 301.3 OR 2017 |
| | FBC-RES. SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED |
| | AND LABELED. THE INSTALLATION MANUALS FOR ALL GAS |
| | APPLIANCES / EQUIPMENT SHALL BE ONSITE AT THE TIME OF |
| | INSPECTION.2017, FBC-RES. SEC.G2408.1 |
| | |
| | 4) SUBMIT CALCULATIONS FOR COMBUSTION AIR PER THE 2017 |
| | FBC-RES. SEC. G 2407.1 AND G2439.4 (CLOTHES DRYERS) |
| | |
| | 5) SUBMIT TWO COPIES OF A HOUSE PLAN SHOWING THE |
| | LOCATION OF THE TANKLESS WATER HEATER AND THE LOCATION |
| | AND DISTANCE OF ANY OPERABLE DOORS OR WINDOWS IN |
| | RELATION TO THE WATER HEATER. THE LOCATION OF THE WATER |
| | HEATER SHALL COMPLY WITH THE MANUFACTURER'S |
| | INSTALLATION INSTRUCTIONS. THE HOUSE PLAN CAN BE HAND |
| | DRAWN. WPB AMEND. TO FBC SEC. 107.2. |
| | |
| | 6) PLANS SUBMITTED ARE NOT SIGNED BY THE PERSON |
| | DESIGNING THE SYSTEM AS REQUIRED. FAC 471, 481 |
| | |
| | 7) VALUE OF JOB IS TOO LOW. $800.00 DOES NOT COVER THE |
| | COST OF THE DRYER AND TANKLESS WATER HEATER ALONE. COST |
| | MUST INCLUDE ALL MATERIAL AND LABOR. FOR OWNER BUILDER |
| | IT SHOULD BE VALUED AS IF WAS CONTRACTED OUT. 109.3 |
| | BUILDING PERMIT VALUATIONS. IF, IN THE OPINION OF THE |
| | BUILDING OFFICIAL, THE CLAIMED VALUATION OF BUILDING, |
| | ALTERATION, STRUCTURE, ELECTRICAL, GAS, MECHANICAL OR |
| | PLUMBING SYSTEMS APPEARS TO BE UNDERESTIMATED ON THE |
| | APPLICATION, THE PERMIT SHALL BE DENIED, UNLESS THE |
| | APPLICANT CAN SHOW DETAILED, QUANTITY ESTIMATES, AND/OR |
| | BONA FIDE SIGNED CONTRACTS (EXCLUDING LAND VALUE) TO |
| | MEET THE APPROVAL OF THE BUILDING OFFICIAL. FOR |
| | PERMITTING PURPOSES, VALUATION OF BUILDINGS AND SYSTEMS |
| | SHALL BE TOTAL REPLACEMENT VALUE TO INCLUDE STRUCTURAL, |
| | ELECTRIC, PLUMBING, MECHANICAL, INTERIOR FINISH, |
| | RELATIVE SITE WORK, ARCHITECTURAL AND DESIGN FEES, |
| | MARKETING COSTS, OVERHEAD AND PROFIT; EXCLUDING ONLY |
| | LAND VALUE. VALUATION REFERENCES MAY INCLUDE THE LATEST |
| | PUBLISHED DATA OF NATIONAL CONSTRUCTION COST ANALYSIS |
| | SERVICES (MARSHALL-SWIFT, MEANS, ETC.), AS PUBLISHED BY |
| | INTERNATIONAL CODE CONGRESS. FINAL BUILDING PERMIT |
| | VALUATION SHALL BE SET BY THE BUILDING OFFICIAL. |
| | |
| | TIM HUNT |
| | PLUMBING PLANS EXAMINER/ PLUMBING INSPECTOR |
| | CITY OF WEST PALM BEACH |
| | 561-248-2703 |
| | [email protected] |
| | [email protected] |
| | |
| | |