Plan Review Notes
Plan Review Notes For Permit 18071331
Permit Number 18071331
Review Stop P
Sequence Number 1
Notes
Date Text
2018-09-07 12:52:48REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-06 11:38:351ST REVIEW: FBC 2017 6TH EDITION
 PERMIT 18071331
 PLUMBING COMMENTS: DENIED
  
 1. REGARDING SANITARY PLUMBING RISER ON PLAN SHEET S1:
 (A) WHAT DOES THE TERM 2" STACK NOTED ON DIAGRAM
 INDICATE? PLEASE CLARIFY.
 (B) AUTOMATIC CLOTHES WASHERS REQUIRE A FIXTURE TRAP
 PER 2017 FBC RES 3201.6 AND A VENT PER 2017 FBC RES
 3105.1. THIS IS NOTED ON A DETAIL ON PLAN SHEET S2 BUT
 MUST ALSO BE SHOWN ON THE SANITARY RISER DIAGRAM ON
 PLAN SHEET S1.
 (C) PLEASE COORDINATE WITH STRUCTURAL TO INSURE THAT
 STRUCTURAL INTEGRITY WILL NOT BE AFFECTED BY PIPING
 (REFER TO 1/4" SCALE "NEW FLOOR PLAN" ON PLAN SHEET
 S1).
  
 2. (A) THERE IS A GAS FIRED TANKLESS WATER HEATER AND A
 GAS DRYER NOTED ON PLAN SHEET S2. A GAS PLAN HAS NOT
 BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. A GAS PLAN
 REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. A SEPARATE
 GAS PERMIT AND PLANS WILL BE REQUIRED FOR A CONTRACTOR
 TO PERFORM THE RELATED WORK PER WPB AMEND. TO FBC SEC.
 105.1. PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT
 SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE
 SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC.
 107.2.1. GAS APPLIANCES SHALL BE LISTED AND LABELED PER
 THE 2017 FBC RES, SEC. G2404.3.
 (B) THE PLANS INDICATE AN EXISTING GAS RANGE. THE BTU
 LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE
 TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING
 SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING
 SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING
 SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS
 THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH
 APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH
 APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF
 PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE
 OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE
 EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE
 SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE
 REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES.
 2017 FBC RES SECS.G2412.4, G2412.8, G2413.1, G2413.2,
 G2413.3.
 (C) A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS
 INSTALLATION OR MODIFICATION OF SYSTEM.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711