| 2018-09-07 12:52:48 | REVIEW COMPLETED BY JERALD SMITH 0017-P |
| 2018-09-06 11:38:35 | 1ST REVIEW: FBC 2017 6TH EDITION |
| | PERMIT 18071331 |
| | PLUMBING COMMENTS: DENIED |
| | |
| | 1. REGARDING SANITARY PLUMBING RISER ON PLAN SHEET S1: |
| | (A) WHAT DOES THE TERM 2" STACK NOTED ON DIAGRAM |
| | INDICATE? PLEASE CLARIFY. |
| | (B) AUTOMATIC CLOTHES WASHERS REQUIRE A FIXTURE TRAP |
| | PER 2017 FBC RES 3201.6 AND A VENT PER 2017 FBC RES |
| | 3105.1. THIS IS NOTED ON A DETAIL ON PLAN SHEET S2 BUT |
| | MUST ALSO BE SHOWN ON THE SANITARY RISER DIAGRAM ON |
| | PLAN SHEET S1. |
| | (C) PLEASE COORDINATE WITH STRUCTURAL TO INSURE THAT |
| | STRUCTURAL INTEGRITY WILL NOT BE AFFECTED BY PIPING |
| | (REFER TO 1/4" SCALE "NEW FLOOR PLAN" ON PLAN SHEET |
| | S1). |
| | |
| | 2. (A) THERE IS A GAS FIRED TANKLESS WATER HEATER AND A |
| | GAS DRYER NOTED ON PLAN SHEET S2. A GAS PLAN HAS NOT |
| | BEEN INCLUDED IN THIS SUBMITTAL PACKAGE. A GAS PLAN |
| | REVIEW HAS NOT BEEN PERFORMED AT THIS TIME. A SEPARATE |
| | GAS PERMIT AND PLANS WILL BE REQUIRED FOR A CONTRACTOR |
| | TO PERFORM THE RELATED WORK PER WPB AMEND. TO FBC SEC. |
| | 105.1. PROVIDE COMPLETE PLANS, APPLIANCE/ EQUIPMENT |
| | SPECIFICATIONS AND GAS RISER THAT REFLECT THE ENTIRE |
| | SCOPE OF GAS WORK TO BE DONE. WPB AMEND. TO FBC SEC. |
| | 107.2.1. GAS APPLIANCES SHALL BE LISTED AND LABELED PER |
| | THE 2017 FBC RES, SEC. G2404.3. |
| | (B) THE PLANS INDICATE AN EXISTING GAS RANGE. THE BTU |
| | LOAD OF THE EXISTING GAS SYSTEM MUST BE ADDED INTO THE |
| | TOTAL BTU LOAD ON THE SYSTEM TO ENSURE THE EXISTING |
| | SYSTEM IS PROPERLY SIZED. IF UNDERSIZED, THE EXISTING |
| | SYSTEM MUST BE REDONE TO ENSURE A SAFE OPERATING |
| | SYSTEM. SUBMIT A GAS PIPING RISER DIAGRAM THAT SHOWS |
| | THE TYPE OF EXISTING APPLIANCE, THE BTU LOAD OF EACH |
| | APPLIANCE, THE PIPE SIZE AND TYPE OF PIPE TO EACH |
| | APPLIANCE, AND THE DISTANCE OF THE LONGEST LENGTH OF |
| | PIPING FROM THE POINT OF DELIVERY TO THE MOST REMOTE |
| | OUTLET AND THE LOAD OF THE SECTION. NOTE: IF THE |
| | EXISTING SYSTEM IS LESS THAN A 2 PSI SYSTEM AND THE |
| | SYSTEM PRESSURE IS INCREASED TO 2 PSI, A LINE PRESSURE |
| | REGULATOR IS REQUIRED AT ALL THE EXISTING APPLIANCES. |
| | 2017 FBC RES SECS.G2412.4, G2412.8, G2413.1, G2413.2, |
| | G2413.3. |
| | (C) A SEPARATE PERMIT AND PLANS IS REQUIRED FOR THE GAS |
| | INSTALLATION OR MODIFICATION OF SYSTEM. |
| | |
| | JERALD SMITH |
| | PLUMBING PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |