| Plan Review Notes For Permit 18071322 |
| Permit Number |
18071322 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-14 15:12:38 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18071322 | | | REVIEWED: AUGUST 9, 2018 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | [FBC R403.4] EXTERIOR FOOTINGS SHALL BE PLACED NOT LESS | | | THAN 12 INCHES BELOW THE UNDISTURBED GROUND SURFACE. | | | THE 6? SLAB IS OK FOR THE GRILLING STATION, BUT IF A | | | TRELLIS IS BEING ATTACHED TO THE COLUMNS THEN THERE | | | WILL BE LATERAL FORCES TO BE COUNTERED. PLEASE ADJUST | | | FUTURE TRELLIS COLUMNS FOR ANTICIPATED LATERAL AND | | | UPLIFT LOADS. | | | | | | NOTE: | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | |
|