Plan Review Notes
Plan Review Notes For Permit 18071301
Permit Number 18071301
Review Stop P
Sequence Number 1
Notes
Date Text
2018-09-07 12:32:20REVIEW COMPLETED BY JERALD SMITH 0017-P
2018-09-04 10:36:531ST REVIEW: FBC 2017 6TH EDITION
  
 PLUMBING COMMENTS: DENIED
  
 1. EACH WET VENTED FIXTURE DRAIN SHALL CONNECT
 INDEPENDENTLY TO THE HORIZONTAL WET VENT PER FBC RES
 P3108.1. THE TUB AND THE SHOWER FIXTURE DRAINS IN
 BATHROOMS ARE CONNECTED TO WATER CLOSET FIXTURE DRAIN;
 THE RESULTING FIXTURE BRANCH IS CONNECTED TO THE WET
 VENT; THIS IS NOT ACCEPTABLE.
  
 2. WATER HEATER IS ON RAISED FLOOR AT SAME ELEVATION AS
 LIVING AREA ADJACENT TO LIVING AREA FLOOR. IF STORAGE
 TYPE THEN PROVIDE PAN PER FBC RES 2801.6.
  
 3. ADDITIONAL INFO/DATA REQUIRED FOR WATER HEATER (FBC
 107.2.1) TO INCLUDE TYPE AND CAPACITY; WATER HEATER
 SHALL COMPLY WITH ENERGY CODE.
  
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711