| Plan Review Notes For Permit 18071291 |
| Permit Number |
18071291 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2018-08-02 10:37:26 | ****CORRECTIONS**** | | | W.P.B. PERMIT: 18051306 | | | | | | DYLAN BATTLES | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | 1. [FBC 107.2.1.2]PROVIDE PRODUCT APPROVAL FOR MULL BAR | | | BETWEEN WINDOW OPENENING 1&6. | | | | | | 2. [FBC R310.2.5]MARK WINDOWS THAT PROVIDE EGRESS FOR | | | EACH BEDROOM. | | | | | | 3. [FBC ENERGY R503.1.1.1]WHERE SOME OR ALL OF AN | | | EXISTING FENESTRATION UNIT IS REPLACED WITH A NEW | | | FENESTRATION PRODUCT, INCLUDING SASH AND GLAZING, THE | | | REPLACEMENT FENESTRATION UNIT SHALL MEET THE APPLICABLE | | | REQUIREMENTS FOR U-FACTOR AND SHGC AS PROVIDED IN TABLE | | | R402.1.2. | | | YOUR WINDOWS SHOULD HAVE U-FACTOR OF 0.75 AND SHGC OF | | | 0.25 | | | | | | NOTE: | | | -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW | | | OF MATERIALS REQUESTED. | | | -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS | | | OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) | | | SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT | | | DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER | | | SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" | | | OR "OLD SHEETS". | | | |
|