Plan Review Notes
Plan Review Notes For Permit 18071267
Permit Number 18071267
Review Stop B
Sequence Number 2
Notes
Date Text
2019-05-07 15:54:06PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
 (REFER TO REVISION #18060327)
  
 1) NOT COMPLIED. THE ENGINEER'S SIGNATURES ON THE TRUSS
 DRAWINGS ARE PHOTO COPIES. FAC 61G15-23.003 PROCEDURES
 FOR PHYSICALLY SIGNING AND SEALING PLANS,
 SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE'S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2) NOT COMPLIED. THE PLANS SPECIFY THE ROOFING MATERIAL
 AS LOW PROFILE CONCRETE ROOF TILE AND THE PRODUCT
 APPROVALS THAT WERE SUBMITTED ARE FOR A CONCRETE TILE
 ROOF. THE TRUSS LAYOUT SPECIFIES THE ROOFING MATERIAL
 AS METAL. COORDINATE AND MAKE THE NECESSARY CORRECTIONS
 AND REVISIONS. FBC 107.2.1
 NOTE: THE COVER SHEET OF THE PLANS SPECIFY THE ROOF
 TRUSS TOP CORD DEAD LOAD AS 20 PSF AND THE BOTTOM CORD
 DEAD LOAD AS 30 PSF. THE TRUSS DOCUMENTS SPECIFY THE
 ROOF TOP CORD DEAD LOAD AS 15 PSF AND THE BOTTOM CORD
 DEAD LIVE LOAD AS 10 PSF. PLEASE CLARIFY.
  
 3) NOT COMPLIED. THE FLOOR FRAMING PLANS SHOW STEEL I
 BEAMS FOR BEAMS 1 AND 2 ON THE FLOOR FRAMING PLAN WHERE
 THE TRUSS LAYOUT PLANS HAVE 3 PLY VERSALAMS. THE
 ENGINEER IS REQUIRED TO PROVIDE SIGNED AND SEALED
 REVISED PLANS FOR THESE CHANGES. FBC 107.2.1
  
 4) OK
  
 5) NOT COMPLIED. THE FLOOR TRUSS LAYOUT PLAN HAS A
 HANGER SCHEDULE THAT SPECIFIES THE HANGERS FOR THE
 GARAGE STORAGE. THE ENGINEER WILL NEED TO TAKE
 RESPONSIBILTY BY SIGNING AND SEALING THE DRAWINGS. FAC
 61G15-23.003.
  
 6) OK
  
  
  
  
  