Plan Review Notes
Plan Review Notes For Permit 18071267
Permit Number 18071267
Review Stop B
Sequence Number 1
Notes
Date Text
2018-07-31 19:27:50PLAN
 REVIEW COMMENTS
  
 1ST REVIEW: FBC FIFTH EDITION (2014)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) THE ENGINEER'S SIGNATURES ON THE TRUSS DRAWINGS ARE
 PHOTO COPIES. FAC 61G15-23.003 PROCEDURES FOR
 PHYSICALLY SIGNING AND SEALING PLANS, SPECIFICATIONS,
 REPORTS OR OTHER DOCUMENTS.
 ENGINEERING PLANS, SPECIFICATIONS, REPORTS OR OTHER
 DOCUMENTS WHICH MUST BE SIGNED, DATED AND SEALED IN
 ACCORDANCE WITH THE PROVISIONS OF SECTION 471.025,
 F.S., AND RULE 61G15-23.001, F.A.C. MUST BE PHYSICALLY
 SIGNED, DATED AND SEALED AS PROVIDED HEREIN BY THE
 PROFESSIONAL ENGINEER IN RESPONSIBLE CHARGE.
 (1) THE LICENSEE SHALL SIGN BY HAND AN ORIGINAL OF THE
 LICENSEE?S SIGNATURE ON EACH PAGE REQUIRED TO BE
 SEALED. A SCANNED, FACSIMILE, DIGITALLY CREATED OR
 COPIED IMAGE OF THE LICENSEE'S SIGNATURE SHALL NOT BE
 USED.
 (2) THE LICENSEE MUST THEN USE A WET SEAL, A DIGITALLY
 CREATED SEAL, OR AN EMBOSSING SEAL PLACED PARTIALLY
 OVERLAPPING THE LICENSEE'S SIGNATURE ON EACH PAGE
 REQUIRED TO BE SEALED. THE PLACEMENT OF THE SEAL SHALL
 NOT RENDER THE SIGNATURE ILLEGIBLE.
  
 2) THE PLANS SPECIFY THE ROOFING MATERIAL AS LOW
 PROFILE CONCRETE ROOF TILE AND THE PRODUCT APPROVALS
 THAT WERE SUBMITTED ARE FOR A CONCRETE TILE ROOF. THE
 TRUSS LAYOUT SPECIFIES THE ROOFING MATERIAL AS METAL.
 COORDINATE AND MAKE THE NECESSARY CORRECTIONS AND
 REVISIONS. FBC 107.2.1
  
 3) THE FLOOR FRAMING PLANS SHOW STEEL I BEAMS FOR BEAMS
 1 AND 2 ON THE FLOOR FRAMING PLAN WHERE THE TRUSS
 LAYOUT PLANS HAVE 3 PLY VERSALAMS. THE ENGINEER IS
 REQUIRED TO PROVIDE SIGNED AND SEALED REVISED PLANS FOR
 THESE CHANGES. FBC 107.2.1
  
 4) THE APPROVED PLANS DO NOT SHOW THE FLOOR TRUSSES FOR
 STORAGE AT THE GARAGE. PLEASE CLARIFY. FBC 107.2.1
  
 5) THE FLOOR TRUSS LAYOUT PLAN HAS A HANGER SCHEDULE
 THAT SPECIFIES THE HANGERS FOR THE GARAGE STORAGE. THE
 ENGINEER WILL NEED TO TAKE RESPONSIBILTY BY SIGNING AND
 SEALING THE DRAWINGS. FAC 61G15-23.003.
  
 6) THE ROOF FRAMING PLAN ON SHEET S2.1 HAS SOME
 DIFFERENCES FROM THE ROOF TRUSS LAYOUT DRAWINGS. THE
 ROOF FRAMING PLAN ON S-2 DOES NOT SPECIFY THE ANCHORS
 FOR THE GIRDER TRUSSES. THE ENGINEER OF RECORD WILL
 ALSO HAVE TO SPECIFY ALL OF THE HANGERS FOR THE ROOF
 AND FLOOR TRUSSES THAT ARE NOT SPECIFIED BY THE TRUSS
 ENGINEER. FBC-R802.1.7.1
  
  
  
  
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved