| Plan Review Notes For Permit 18071182 |
| Permit Number |
18071182 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2018-10-22 17:01:49 | ****CORRECTIONS**** | | | | | | PETER E VALENTI | | | BUILDING PLANS EXAMINER | | | [email protected] | | | 561-805-6673 | | | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | | FBC B = FBC BUILDING | | | FBC EB = FBC EXISTING BUILDING | | | FBC A = FBC ACCESSIBILITY | | | FBC EC = FBC ENERGY CONSERVATION | | | FBC R = FBC RESIDENTIAL | | | | | | THE COMMENTS FROM THE LAST REVIEW HAVE NOT BEEN | | | COMPLETELY ADDRESSED. | | | PLEASE REVIEW LAST PACKAGE OF SUBMITTED PLANS AND | | | SPECIFICATIONS INCLUDING THE FOLLOWING COMMENTS LISTED | | | BELOW, ADDRESS THE COMMENTS AND RESUBMIT. | | | | | | FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL | | | INFORMATION, DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING | | | DATA SHALL BEAR THE NAME OF THE PERSON RESPONSIBLE FOR | | | THE DESIGN. THERE ARE SEVERAL SIGNATURES FROM DIFFERENT | | | INDIVIDUALS ON THE SUBMITTED PLAN INFORMATION. THESE | | | SUBMITTED PLANS AND SPECIFICATIONS NEED TO BE SIGNED | | | AND SEALED BY THE DESIGN PROFESSIONAL OF RECORD. | | | | | | FBC 603.1 FLAME SPREAD FOR THE UNDERLAYMENT INSTALLED | | | WITH THE WOOD FLOORING STILL NEEDS TO BE TESTED PER | | | SECTION 603.1. THE TEST PROCEDURE THAT WAS SUBMITTED | | | WAS TESTED PER SECTION 804.3. |
|