Plan Review Notes
Plan Review Notes For Permit 18071182
Permit Number 18071182
Review Stop B
Sequence Number 3
Notes
Date Text
2018-10-22 17:01:49****CORRECTIONS****
  
 PETER E VALENTI
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6673
  
 FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
 FBC R = FBC RESIDENTIAL
  
 THE COMMENTS FROM THE LAST REVIEW HAVE NOT BEEN
 COMPLETELY ADDRESSED.
 PLEASE REVIEW LAST PACKAGE OF SUBMITTED PLANS AND
 SPECIFICATIONS INCLUDING THE FOLLOWING COMMENTS LISTED
 BELOW, ADDRESS THE COMMENTS AND RESUBMIT.
  
 FBC 107.2.1 INFORMATION ON CONSTRUCTION DOCUMENTS. ALL
 INFORMATION, DRAWINGS, SPECIFICATIONS, AND ACCOMPANYING
 DATA SHALL BEAR THE NAME OF THE PERSON RESPONSIBLE FOR
 THE DESIGN. THERE ARE SEVERAL SIGNATURES FROM DIFFERENT
 INDIVIDUALS ON THE SUBMITTED PLAN INFORMATION. THESE
 SUBMITTED PLANS AND SPECIFICATIONS NEED TO BE SIGNED
 AND SEALED BY THE DESIGN PROFESSIONAL OF RECORD.
  
 FBC 603.1 FLAME SPREAD FOR THE UNDERLAYMENT INSTALLED
 WITH THE WOOD FLOORING STILL NEEDS TO BE TESTED PER
 SECTION 603.1. THE TEST PROCEDURE THAT WAS SUBMITTED
 WAS TESTED PER SECTION 804.3.